2021-06-10 20:00:51 +00:00
{
"CVE_data_meta" : {
2021-10-26 11:49:04 +02:00
"ASSIGNER" : "info@cert.vde.com" ,
"DATE_PUBLIC" : "2021-10-25T14:00:00.000Z" ,
2021-06-10 20:00:51 +00:00
"ID" : "CVE-2021-34593" ,
2021-10-26 11:49:04 +02:00
"STATE" : "PUBLIC" ,
"TITLE" : "CODESYS V2 runtime: unauthenticated invalid requests may result in denial-of-service"
2021-06-10 20:00:51 +00:00
} ,
2021-10-26 11:49:04 +02:00
"affects" : {
"vendor" : {
"vendor_data" : [
{
"product" : {
"product_data" : [
{
"product_name" : "CODESYS V2 " ,
"version" : {
"version_data" : [
{
"version_affected" : "<" ,
"version_name" : "Runtime Toolkit 32 bit full" ,
"version_value" : "V2.4.7.56"
} ,
{
"version_affected" : "<" ,
"version_name" : "PLCWinNT" ,
"version_value" : "V2.4.7.56"
}
]
}
}
]
} ,
"vendor_name" : "CODESYS"
}
]
}
} ,
"credit" : [
{
"lang" : "eng" ,
"value" : "This issue was discovered by Steffen Robertz and Gerhard Hechenberger from the SEC Consult Vulnerability Lab."
}
] ,
"data_format" : "MITRE" ,
"data_type" : "CVE" ,
"data_version" : "4.0" ,
2021-06-10 20:00:51 +00:00
"description" : {
"description_data" : [
{
"lang" : "eng" ,
2021-10-26 11:49:04 +02:00
"value" : "In CODESYS V2 Runtime Toolkit 32 Bit full and PLCWinNT prior to versions V2.4.7.56 unauthenticated crafted invalid requests may result in several denial-of-service conditions. Running PLC programs may be stopped, memory may be leaked, or further communication clients may be blocked from accessing the PLC."
}
]
} ,
"generator" : {
"engine" : "Vulnogram 0.0.9"
} ,
"impact" : {
"cvss" : {
"attackComplexity" : "LOW" ,
"attackVector" : "NETWORK" ,
"availabilityImpact" : "HIGH" ,
"baseScore" : 7.5 ,
"baseSeverity" : "HIGH" ,
"confidentialityImpact" : "NONE" ,
"integrityImpact" : "NONE" ,
"privilegesRequired" : "NONE" ,
"scope" : "UNCHANGED" ,
"userInteraction" : "NONE" ,
"vectorString" : "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H" ,
"version" : "3.1"
}
} ,
"problemtype" : {
"problemtype_data" : [
{
"description" : [
{
"lang" : "eng" ,
"value" : "CWE-755 Improper Handling of Exceptional Conditions"
}
]
2021-06-10 20:00:51 +00:00
}
]
2021-10-26 11:49:04 +02:00
} ,
"references" : {
"reference_data" : [
{
"name" : "https://customers.codesys.com/index.php?eID=dumpFile&t=f&f=16877&token=8faab0fc1e069f4edfca5d5aba8146139f67a175&download=" ,
"refsource" : "CONFIRM" ,
"url" : "https://customers.codesys.com/index.php?eID=dumpFile&t=f&f=16877&token=8faab0fc1e069f4edfca5d5aba8146139f67a175&download="
2021-11-17 15:47:33 -05:00
} ,
{
"refsource" : "FULLDISC" ,
"name" : "20211029 SEC Consult SA-20211028-0 :: Denial of Service in CODESYS V2" ,
"url" : "http://seclists.org/fulldisclosure/2021/Oct/64"
} ,
{
"refsource" : "MISC" ,
"name" : "http://packetstormsecurity.com/files/164716/CODESYS-2.4.7.0-Denial-Of-Service.html" ,
"url" : "http://packetstormsecurity.com/files/164716/CODESYS-2.4.7.0-Denial-Of-Service.html"
2022-02-04 20:01:16 +00:00
} ,
{
"refsource" : "MISC" ,
"name" : "http://packetstormsecurity.com/files/165874/WAGO-750-8xxx-PLC-Denial-Of-Service-User-Enumeration.html" ,
"url" : "http://packetstormsecurity.com/files/165874/WAGO-750-8xxx-PLC-Denial-Of-Service-User-Enumeration.html"
2021-10-26 11:49:04 +02:00
}
]
} ,
"solution" : [
{
"lang" : "eng" ,
"value" : "CODESYS GmbH has released the following product versions to solve the noted vulnerability issue for the affected CODESYS products:\n * CODESYS Runtime Toolkit 32 bit full version V2.4.7.56\n * CODESYS PLCWinNT version V2.4.7.56. This will also be part of the CODESYS Development System setup version V2.3.9.68."
}
] ,
"source" : {
"defect" : [
"VDE-2021-049"
] ,
"discovery" : "EXTERNAL"
2021-06-10 20:00:51 +00:00
}
}