mirror of
https://github.com/CVEProject/cvelist.git
synced 2025-07-29 05:56:59 +00:00
"-Synchronized-Data."
This commit is contained in:
parent
77b5797ba0
commit
203073d384
@ -1,17 +1,93 @@
|
||||
{
|
||||
"data_version": "4.0",
|
||||
"data_type": "CVE",
|
||||
"data_format": "MITRE",
|
||||
"data_version": "4.0",
|
||||
"CVE_data_meta": {
|
||||
"ID": "CVE-2023-2186",
|
||||
"ASSIGNER": "cve@mitre.org",
|
||||
"STATE": "RESERVED"
|
||||
"ASSIGNER": "trellixpsirt@trellix.com",
|
||||
"STATE": "PUBLIC"
|
||||
},
|
||||
"description": {
|
||||
"description_data": [
|
||||
{
|
||||
"lang": "eng",
|
||||
"value": "** RESERVED ** This candidate has been reserved by an organization or individual that will use it when announcing a new security problem. When the candidate has been publicized, the details for this candidate will be provided."
|
||||
"value": "On Triangle MicroWorks' SCADA Data Gateway version <= v5.01.03, an unauthenticated attacker can send a specially crafted broadcast message including format string characters to the SCADA Data Gateway to perform unrestricted memory reads.An unauthenticated user can use this format string vulnerability to repeatedly crash the GTWWebMonitor.exe process to DoS the Web Monitor. Furthermore, an authenticated user can leverage this vulnerability to leak memory from the GTWWebMonitor.exe process. This could be leveraged in an exploit chain to gain code execution."
|
||||
}
|
||||
]
|
||||
},
|
||||
"problemtype": {
|
||||
"problemtype_data": [
|
||||
{
|
||||
"description": [
|
||||
{
|
||||
"lang": "eng",
|
||||
"value": "CWE-134 Use of Externally-Controlled Format String",
|
||||
"cweId": "CWE-134"
|
||||
}
|
||||
]
|
||||
}
|
||||
]
|
||||
},
|
||||
"affects": {
|
||||
"vendor": {
|
||||
"vendor_data": [
|
||||
{
|
||||
"vendor_name": "Triangle MicroWorks",
|
||||
"product": {
|
||||
"product_data": [
|
||||
{
|
||||
"product_name": "SCADA Data Gateway",
|
||||
"version": {
|
||||
"version_data": [
|
||||
{
|
||||
"version_affected": "=",
|
||||
"version_value": "5.01.03"
|
||||
}
|
||||
]
|
||||
}
|
||||
}
|
||||
]
|
||||
}
|
||||
}
|
||||
]
|
||||
}
|
||||
},
|
||||
"references": {
|
||||
"reference_data": [
|
||||
{
|
||||
"url": "https://www.trellix.com/en-us/about/newsroom/stories/research/industrial-and-manufacturing-cves.html",
|
||||
"refsource": "MISC",
|
||||
"name": "https://www.trellix.com/en-us/about/newsroom/stories/research/industrial-and-manufacturing-cves.html"
|
||||
}
|
||||
]
|
||||
},
|
||||
"generator": {
|
||||
"engine": "Vulnogram 0.1.0-dev"
|
||||
},
|
||||
"source": {
|
||||
"discovery": "UNKNOWN"
|
||||
},
|
||||
"credits": [
|
||||
{
|
||||
"lang": "en",
|
||||
"value": "Sam Quinn"
|
||||
}
|
||||
],
|
||||
"impact": {
|
||||
"cvss": [
|
||||
{
|
||||
"attackComplexity": "LOW",
|
||||
"attackVector": "NETWORK",
|
||||
"availabilityImpact": "HIGH",
|
||||
"baseScore": 8.2,
|
||||
"baseSeverity": "HIGH",
|
||||
"confidentialityImpact": "LOW",
|
||||
"integrityImpact": "NONE",
|
||||
"privilegesRequired": "NONE",
|
||||
"scope": "UNCHANGED",
|
||||
"userInteraction": "NONE",
|
||||
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:L/I:N/A:H",
|
||||
"version": "3.1"
|
||||
}
|
||||
]
|
||||
}
|
||||
|
@ -1,17 +1,93 @@
|
||||
{
|
||||
"data_version": "4.0",
|
||||
"data_type": "CVE",
|
||||
"data_format": "MITRE",
|
||||
"data_version": "4.0",
|
||||
"CVE_data_meta": {
|
||||
"ID": "CVE-2023-2187",
|
||||
"ASSIGNER": "cve@mitre.org",
|
||||
"STATE": "RESERVED"
|
||||
"ASSIGNER": "trellixpsirt@trellix.com",
|
||||
"STATE": "PUBLIC"
|
||||
},
|
||||
"description": {
|
||||
"description_data": [
|
||||
{
|
||||
"lang": "eng",
|
||||
"value": "** RESERVED ** This candidate has been reserved by an organization or individual that will use it when announcing a new security problem. When the candidate has been publicized, the details for this candidate will be provided."
|
||||
"value": "On Triangle MicroWorks' SCADA Data Gateway version <= v5.01.03, an unauthenticated attacker can send broadcast events to any user via the WebMonitor.An unauthenticated user can use this vulnerability to forcefully log out of any currently logged-in user by sending a \"password change event\". Furthermore, an attacker could use this vulnerability to spam the logged-in user with false events."
|
||||
}
|
||||
]
|
||||
},
|
||||
"problemtype": {
|
||||
"problemtype_data": [
|
||||
{
|
||||
"description": [
|
||||
{
|
||||
"lang": "eng",
|
||||
"value": "CWE-306: Missing Authentication for Critical function\u00a0",
|
||||
"cweId": "CWE-306"
|
||||
}
|
||||
]
|
||||
}
|
||||
]
|
||||
},
|
||||
"affects": {
|
||||
"vendor": {
|
||||
"vendor_data": [
|
||||
{
|
||||
"vendor_name": "Triangle MicroWorks",
|
||||
"product": {
|
||||
"product_data": [
|
||||
{
|
||||
"product_name": "SCADA Data Gateway",
|
||||
"version": {
|
||||
"version_data": [
|
||||
{
|
||||
"version_affected": "=",
|
||||
"version_value": "5.01.03"
|
||||
}
|
||||
]
|
||||
}
|
||||
}
|
||||
]
|
||||
}
|
||||
}
|
||||
]
|
||||
}
|
||||
},
|
||||
"references": {
|
||||
"reference_data": [
|
||||
{
|
||||
"url": "https://www.trellix.com/en-us/about/newsroom/stories/research/industrial-and-manufacturing-cves.html",
|
||||
"refsource": "MISC",
|
||||
"name": "https://www.trellix.com/en-us/about/newsroom/stories/research/industrial-and-manufacturing-cves.html"
|
||||
}
|
||||
]
|
||||
},
|
||||
"generator": {
|
||||
"engine": "Vulnogram 0.1.0-dev"
|
||||
},
|
||||
"source": {
|
||||
"discovery": "UNKNOWN"
|
||||
},
|
||||
"credits": [
|
||||
{
|
||||
"lang": "en",
|
||||
"value": "Philippe Laulheret"
|
||||
}
|
||||
],
|
||||
"impact": {
|
||||
"cvss": [
|
||||
{
|
||||
"attackComplexity": "LOW",
|
||||
"attackVector": "NETWORK",
|
||||
"availabilityImpact": "LOW",
|
||||
"baseScore": 5.3,
|
||||
"baseSeverity": "MEDIUM",
|
||||
"confidentialityImpact": "NONE",
|
||||
"integrityImpact": "NONE",
|
||||
"privilegesRequired": "NONE",
|
||||
"scope": "UNCHANGED",
|
||||
"userInteraction": "NONE",
|
||||
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L",
|
||||
"version": "3.1"
|
||||
}
|
||||
]
|
||||
}
|
||||
|
Loading…