{ "data_type": "CVE", "data_format": "MITRE", "data_version": "4.0", "CVE_data_meta": { "ID": "CVE-2019-6828", "ASSIGNER": "cybersecurity@schneider-electric.com", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "vendor_name": "Schneider Electric SE", "product": { "product_data": [ { "product_name": "Modicon M580", "version": { "version_data": [ { "version_value": "firmware version prior to V2.90" } ] } }, { "product_name": "Modicon M340", "version": { "version_data": [ { "version_value": "firmware version prior to V3.10" } ] } }, { "product_name": "Modicon Premium", "version": { "version_data": [ { "version_value": "all versions" } ] } }, { "product_name": "Modicon Quantum", "version": { "version_data": [ { "version_value": "all versions" } ] } } ] } } ] } }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-248: Uncaught Exception" } ] } ] }, "references": { "reference_data": [ { "refsource": "CONFIRM", "name": "https://www.schneider-electric.com/en/download/document/SEVD-2019-134-11/", "url": "https://www.schneider-electric.com/en/download/document/SEVD-2019-134-11/" } ] }, "description": { "description_data": [ { "lang": "eng", "value": "A CWE-248: Uncaught Exception vulnerability exists Modicon M580 (firmware version prior to V2.90), Modicon M340 (firmware version prior to V3.10), Modicon Premium (all versions), and Modicon Quantum (all versions), which could cause a possible denial of service when reading specific coils and registers in the controller over Modbus." } ] } }