{ "CVE_data_meta" : { "ASSIGNER" : "ics-cert@hq.dhs.gov", "DATE_PUBLIC" : "2018-04-17T00:00:00", "ID" : "CVE-2018-7522", "STATE" : "PUBLIC" }, "affects" : { "vendor" : { "vendor_data" : [ { "product" : { "product_data" : [ { "product_name" : "Triconex Tricon", "version" : { "version_data" : [ { "version_value" : "MP model 3008 firmware versions 10.0-10.4" } ] } } ] }, "vendor_name" : "Schneider Electric" } ] } }, "data_format" : "MITRE", "data_type" : "CVE", "data_version" : "4.0", "description" : { "description_data" : [ { "lang" : "eng", "value" : "In Schneider Electric Triconex Tricon MP model 3008 firmware versions 10.0-10.4, when a system call is made, registers are stored to a fixed memory location. Modifying the data in this location could allow attackers to gain supervisor-level access and control system states." } ] }, "problemtype" : { "problemtype_data" : [ { "description" : [ { "lang" : "eng", "value" : "Improper Restriction Of Operations Within The Bounds Of A Memory Buffer CWE-119" } ] } ] }, "references" : { "reference_data" : [ { "name" : "https://ics-cert.us-cert.gov/advisories/ICSA-18-107-02", "refsource" : "MISC", "url" : "https://ics-cert.us-cert.gov/advisories/ICSA-18-107-02" }, { "name" : "https://www.schneider-electric.com/en/download/document/SEVD-2017-347-01/", "refsource" : "CONFIRM", "url" : "https://www.schneider-electric.com/en/download/document/SEVD-2017-347-01/" }, { "name" : "103947", "refsource" : "BID", "url" : "http://www.securityfocus.com/bid/103947" } ] } }