{ "data_version": "4.0", "data_type": "CVE", "data_format": "MITRE", "CVE_data_meta": { "ID": "CVE-2024-6207", "ASSIGNER": "PSIRT@rockwellautomation.com", "STATE": "PUBLIC" }, "description": { "description_data": [ { "lang": "eng", "value": "CVE 2021-22681 https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.PN1550.html \u00a0and send a specially crafted CIP message to the device. If exploited, a threat actor could help prevent access to the legitimate user and end connections to connected devices including the workstation. To recover the controllers, a download is required which ends any process that the controller is running." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-20 Improper Input Validation", "cweId": "CWE-20" } ] } ] }, "affects": { "vendor": { "vendor_data": [ { "vendor_name": "Rockwell Automation", "product": { "product_data": [ { "product_name": "ControlLogix\u00ae 5580", "version": { "version_data": [ { "version_affected": "=", "version_value": "V28.011" } ] } }, { "product_name": "ControlLogix\u00ae 5580 Process", "version": { "version_data": [ { "version_affected": "=", "version_value": "V33.011" } ] } }, { "product_name": "GuardLogix 5580", "version": { "version_data": [ { "version_affected": "=", "version_value": "V31.011" } ] } }, { "product_name": "CompactLogix 5380", "version": { "version_data": [ { "version_affected": "=", "version_value": "V28.011" } ] } }, { "product_name": "Compact GuardLogix 5380 SIL 2", "version": { "version_data": [ { "version_affected": "=", "version_value": "V31.011" } ] } }, { "product_name": "Compact GuardLogix 5380 SIL 3", "version": { "version_data": [ { "version_affected": "=", "version_value": "V32.013" } ] } }, { "product_name": "CompactLogix 5480", "version": { "version_data": [ { "version_affected": "=", "version_value": "V32.011" } ] } }, { "product_name": "FactoryTalk\u00ae Logix Echo", "version": { "version_data": [ { "version_affected": "=", "version_value": "V33.011" } ] } } ] } } ] } }, "references": { "reference_data": [ { "url": "https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1707.html", "refsource": "MISC", "name": "https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1707.html" } ] }, "generator": { "engine": "Vulnogram 0.2.0" }, "source": { "discovery": "INTERNAL" }, "solution": [ { "lang": "en", "supportingMedia": [ { "base64": false, "type": "text/html", "value": "
AFFECTED PRODUCTS AND SOLUTION
Affected Product | First Known in firmware revision | Corrected in firmware revision |
ControlLogix\u00ae 5580 | V28.011 | V33.017, V34.014, V35.013, V36.011 and later |
ControlLogix\u00ae 5580 Process | V33.011 | V33.017, V34.014, V35.013, V36.011 and later |
GuardLogix 5580 | V31.011 | V33.017, V34.014, V35.013, V36.011 and later |
CompactLogix 5380 | V28.011 | V33.017, V34.014, V35.013, V36.011 and later |
Compact GuardLogix 5380 SIL 2 | V31.011 | V33.017, V34.014, V35.013, V36.011 and later |
Compact GuardLogix 5380 SIL 3 | V32.013 | V33.017, V34.014, V35.013, V36.011 and later |
CompactLogix 5480 | V32.011 | V33.017, V34.014, V35.013, V36.011 and later |
FactoryTalk\u00ae Logix Echo | V33.011 | V34.014, V35.013, V36.011 and later |