{ "CVE_data_meta": { "ASSIGNER": "productcert@siemens.com", "ID": "CVE-2019-19279", "STATE": "PUBLIC" }, "data_format": "MITRE", "data_version": "4.0", "data_type": "CVE", "affects": { "vendor": { "vendor_data": [ { "vendor_name": "Siemens AG", "product": { "product_data": [ { "product_name": "SIPROTEC 4 and SIPROTEC Compact relays equipped with EN100 Ethernet communication modules", "version": { "version_data": [ { "version_value": "All versions" } ] } } ] } } ] } }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-20: Improper Input Validation" } ] } ] }, "description": { "description_data": [ { "lang": "eng", "value": "A vulnerability has been identified in SIPROTEC 4 and SIPROTEC Compact relays equipped with EN100 Ethernet communication modules (All versions). Specially crafted packets sent to port 50000/UDP of the EN100 Ethernet communication modules could cause a Denial-of-Service of the affected device. A manual reboot is required to recover the service of the device. At the time of advisory publication no public exploitation of this security vulnerability was known to Siemens." } ] }, "references": { "reference_data": [ { "refsource": "MISC", "url": "https://cert-portal.siemens.com/productcert/pdf/ssa-974843.pdf", "name": "https://cert-portal.siemens.com/productcert/pdf/ssa-974843.pdf" } ] } }