{ "CVE_data_meta": { "ASSIGNER": "ics-cert@hq.dhs.gov", "ID": "CVE-2016-7987", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "product": { "product_data": [ { "product_name": "Siemens SICAM RTU Devices before 08", "version": { "version_data": [ { "version_value": "Siemens SICAM RTU Devices before 08" } ] } } ] }, "vendor_name": "n/a" } ] } }, "data_format": "MITRE", "data_type": "CVE", "data_version": "4.0", "description": { "description_data": [ { "lang": "eng", "value": "An issue was discovered in Siemens ETA4 firmware (all versions prior to Revision 08) of the SM-2558 extension module for: SICAM AK, SICAM TM 1703, SICAM BC 1703, and SICAM AK 3. Specially crafted packets sent to Port 2404/TCP could cause the affected device to go into defect mode. A cold start might be required to recover the system, a Denial-of-Service Vulnerability." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "Siemens SICAM RTU Devices Denial-of-Service Vulnerability" } ] } ] }, "references": { "reference_data": [ { "name": "93832", "refsource": "BID", "url": "http://www.securityfocus.com/bid/93832" }, { "name": "https://ics-cert.us-cert.gov/advisories/ICSA-16-299-01", "refsource": "MISC", "url": "https://ics-cert.us-cert.gov/advisories/ICSA-16-299-01" } ] } }