{ "data_version": "4.0", "data_type": "CVE", "data_format": "MITRE", "CVE_data_meta": { "ID": "CVE-2023-0811", "ASSIGNER": "ics-cert@hq.dhs.gov", "STATE": "PUBLIC" }, "description": { "description_data": [ { "lang": "eng", "value": "Omron CJ1M unit v4.0 and prior has improper access controls on the memory region where the UM password is stored. If an adversary issues a PROGRAM AREA WRITE command to a specific memory region, they could overwrite the password. This may lead to disabling UM protections or setting a non-ASCII password (non-keyboard characters) and preventing an engineer from viewing or modifying the user program." } ] }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "CWE-284 Improper Access Control ", "cweId": "CWE-284" } ] } ] }, "affects": { "vendor": { "vendor_data": [ { "vendor_name": "Omron ", "product": { "product_data": [ { "product_name": "CJ1M SYSMAC CJ-series", "version": { "version_data": [ { "version_affected": "=", "version_value": "All versions " } ] } }, { "product_name": "CJ1M SYSMAC CS-series ", "version": { "version_data": [ { "version_affected": "=", "version_value": "All versions " }, { "version_affected": "=", "version_value": "All versions " }, { "version_affected": "=", "version_value": "All versions " }, { "version_affected": "=", "version_value": "All versions " }, { "version_affected": "=", "version_value": "All versions " }, { "version_affected": "=", "version_value": "All versions " } ] } } ] } }, { "vendor_name": "Omron", "product": { "product_data": [ { "product_name": "CJ1M SYSMAC CJ-series", "version": { "version_data": [ { "version_affected": "=", "version_value": "All versions " }, { "version_affected": "=", "version_value": "All versions " }, { "version_affected": "=", "version_value": "All versions " } ] } }, { "product_name": "CJ1M SYSMAC CS-series ", "version": { "version_data": [ { "version_affected": "=", "version_value": "All versions " } ] } }, { "product_name": "CJ1M SYSMAC CP-series", "version": { "version_data": [ { "version_affected": "=", "version_value": "All versions " }, { "version_affected": "=", "version_value": "All versions " }, { "version_affected": "=", "version_value": "All versions " }, { "version_affected": "=", "version_value": "All versions " }, { "version_affected": "=", "version_value": "All versions " }, { "version_affected": "=", "version_value": "All versions " }, { "version_affected": "=", "version_value": "All versions " }, { "version_affected": "=", "version_value": "All versions " }, { "version_affected": "=", "version_value": "All versions " }, { "version_affected": "=", "version_value": "All versions " }, { "version_affected": "=", "version_value": "All versions " }, { "version_affected": "=", "version_value": "All versions " } ] } } ] } } ] } }, "references": { "reference_data": [ { "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-23-073-01", "refsource": "MISC", "name": "https://www.cisa.gov/news-events/ics-advisories/icsa-23-073-01" }, { "url": "https://www.ia.omron.com/product/vulnerability/OMSR-2023-001_en.pdf", "refsource": "MISC", "name": "https://www.ia.omron.com/product/vulnerability/OMSR-2023-001_en.pdf" } ] }, "generator": { "engine": "Vulnogram 0.1.0-dev" }, "source": { "discovery": "UNKNOWN" }, "work_around": [ { "lang": "en", "supportingMedia": [ { "base64": false, "type": "text/html", "value": "\n\n

OMRON has released the following countermeasures for users to implement:

If the countermeasures cannot be applied, OMRON recommends that customers take the following mitigation measures:

Security measures to prevent unauthorized access:

For more information, see Omron\u2019s Security Advisory.


\n\n
" } ], "value": "\nOMRON has released the following countermeasures for users to implement: \n\n * Enable the hardware switch to prohibit writing UM (DIP switch on front panel of the CPU Unit) \n * Set UM read protection password and \u201cProhibit from overwriting to a protected program \u201coption. \n\n\nIf the countermeasures cannot be applied, OMRON recommends that customers take the following mitigation measures: \n\nSecurity measures to prevent unauthorized access: \n\n * If the following products and versions are used, the risk of attacks by an attacker via the network can be reduced by taking the following measures. * Enable the FINS write protection function. \n * Select the Protect by IP Address \n\n\n\n * Minimize connection of control systems and equipment to open networks, so that untrusted devices will be unable to access them. \u00a0\n * Implement firewalls (by shutting down unused communications ports, limiting communications hosts, limiting access to FINS port (9600)) and isolate them from the IT network. \n * Use a virtual private network (VPN) for remote access to control systems and equipment. \n * Use strong passwords and change them frequently. \n * Install physical controls so that only authorized personnel can access control systems and equipment. \n * Scan virus to ensure safety of any USB drives or similar devices before connecting them to systems and devices. \n * Enforce multifactor authentication to all devices with remote access to control systems and equipment whenever possible. \n * Anti-virus protection * Protect any PC with access to the control system against malware and ensure installation and maintenance of up-to-date commercial grade anti-virus software protection. \n\n\n\n * Data input and output protection * Validation processing such as backup and range check to cope with unintentional modification of input/output data to control systems and devices. \n\n\n\n * Data recovery * Periodical data backup and maintenance to prepare for data loss. \n\n\n\n\n\nFor more information, see Omron\u2019s Security Advisory https://www.ia.omron.com/product/vulnerability/OMSR-2023-001_en.pdf .\n\n\n\n\n\n" } ], "credits": [ { "lang": "en", "value": "Sam Hanson of Dragos reported these vulnerabilities to CISA. " } ], "impact": { "cvss": [ { "attackComplexity": "LOW", "attackVector": "NETWORK", "availabilityImpact": "HIGH", "baseScore": 9.1, "baseSeverity": "CRITICAL", "confidentialityImpact": "NONE", "integrityImpact": "HIGH", "privilegesRequired": "NONE", "scope": "UNCHANGED", "userInteraction": "NONE", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H", "version": "3.1" } ] } }