{ "data_type": "CVE", "data_format": "MITRE", "data_version": "4.0", "CVE_data_meta": { "ID": "CVE-2019-6811", "ASSIGNER": "cybersecurity@schneider-electric.com", "STATE": "PUBLIC" }, "affects": { "vendor": { "vendor_data": [ { "vendor_name": "Schneider Electric SE", "product": { "product_data": [ { "product_name": "Modicon Quantum 140 NOE771x1", "version": { "version_data": [ { "version_value": "version 6.9 and earlier" } ] } } ] } } ] } }, "problemtype": { "problemtype_data": [ { "description": [ { "lang": "eng", "value": "Improper Check for Unusual or Exceptional Conditions (CWE-754) " } ] } ] }, "references": { "reference_data": [ { "refsource": "CONFIRM", "name": "https://www.schneider-electric.com/en/download/document/SEVD-2019-253-02/", "url": "https://www.schneider-electric.com/en/download/document/SEVD-2019-253-02/" } ] }, "description": { "description_data": [ { "lang": "eng", "value": "An Improper Check for Unusual or Exceptional Conditions (CWE-754) vulnerability exists in Modicon Quantum 140 NOE771x1 version 6.9 and earlier, which could cause denial of service when the module receives an IP fragmented packet with a length greater than 65535 bytes. The module then requires a power cycle to recover." } ] } }