cvelist/2024/32xxx/CVE-2024-32752.json
2024-06-06 21:00:34 +00:00

95 lines
3.8 KiB
JSON

{
"data_version": "4.0",
"data_type": "CVE",
"data_format": "MITRE",
"CVE_data_meta": {
"ID": "CVE-2024-32752",
"ASSIGNER": "productsecurity@jci.com",
"STATE": "PUBLIC"
},
"description": {
"description_data": [
{
"lang": "eng",
"value": "Under certain circumstances communications between the ICU tool and an iSTAR Pro door controller is susceptible to Machine-in-the-Middle attacks which could impact door control and configuration."
}
]
},
"problemtype": {
"problemtype_data": [
{
"description": [
{
"lang": "eng",
"value": "CWE-306 Missing Authentication for Critical Function",
"cweId": "CWE-306"
}
]
}
]
},
"affects": {
"vendor": {
"vendor_data": [
{
"vendor_name": "Johnson Controls",
"product": {
"product_data": [
{
"product_name": "Software House iSTAR Pro, ICU",
"version": {
"version_data": [
{
"version_affected": "<=",
"version_name": "0",
"version_value": "ALL"
}
]
}
}
]
}
}
]
}
},
"references": {
"reference_data": [
{
"url": "https://www.johnsoncontrols.com/-/media/jci/cyber-solutions/product-security-advisories/2024/jci-psa-2024-06.pdf",
"refsource": "MISC",
"name": "https://www.johnsoncontrols.com/-/media/jci/cyber-solutions/product-security-advisories/2024/jci-psa-2024-06.pdf"
},
{
"url": "https://www.cisa.gov/news-events/ics-advisories/icsa-24-158-04",
"refsource": "MISC",
"name": "https://www.cisa.gov/news-events/ics-advisories/icsa-24-158-04"
}
]
},
"generator": {
"engine": "Vulnogram 0.2.0"
},
"source": {
"discovery": "EXTERNAL"
},
"solution": [
{
"lang": "en",
"supportingMedia": [
{
"base64": false,
"type": "text/html",
"value": "\n\n<span style=\"background-color: rgb(255, 255, 255);\">The iSTAR Pro controller has reached its end-of-support period and no further firmware updates will be provided. However, the iSTAR Pro has a physical dip switch located on its GCM board, labeled S4, that can be configured to block out communications to the ICU tool. Please consult the iSTAR Pro Installation and Configuration Guide for more details on how to set the dip switch to mitigate this vulnerability. </span>\n\n<br>"
}
],
"value": "The iSTAR Pro controller has reached its end-of-support period and no further firmware updates will be provided. However, the iSTAR Pro has a physical dip switch located on its GCM board, labeled S4, that can be configured to block out communications to the ICU tool. Please consult the iSTAR Pro Installation and Configuration Guide for more details on how to set the dip switch to mitigate this vulnerability."
}
],
"credits": [
{
"lang": "en",
"value": "Reid Wightman of Dragos"
}
]
}