"CVE_data_meta": {
"ASSIGNER": "cybersecurity@hitachienergy.com",
"DATE_PUBLIC": "2022-09-06T14:30:00.000Z",
"ID": "CVE-2022-29492",
"STATE": "PUBLIC",
"TITLE": "A vulnerability exists in the handling of a malformed IEC 104 TCP packet. Upon receiving a malformed IEC 104 TCP packet, the malformed packet is dropped, however the TCP connection is left open. This may cause a denial-of-service if the affected connection is left open."
},
"affects": {
"vendor": {
"vendor_data": [
{
"product": {
"product_data": [
{
"product_name": "MicroSCADA X SYS600",
"version": {
"version_data": [
{
"version_affected": "=",
"version_value": "10"
},
{
"version_affected": "=",
"version_value": "10.1"
},
{
"version_affected": "=",
"version_value": "10.1.1"
},
{
"version_affected": "=",
"version_value": "10.2"
},
{
"version_affected": "=",
"version_value": "10.2.1"
},
{
"version_affected": "=",
"version_value": "10.3"
},
{
"version_affected": "=",
"version_value": "10.3.1"
}
]
}
},
{
"product_name": "MicroSCADA Pro SYS600",
"version": {
"version_data": [
{
"version_affected": "<=",
"version_value": "9.2 FP2 Hotfix 4"
}
]
}
}
]
},
"vendor_name": "Hitachi Energy"
}
]
}
},
"data_format": "MITRE",
"data_type": "CVE",
"data_version": "4.0",
"description": {
"description_data": [
{
"lang": "eng",
"value": "Improper Input Validation vulnerability in the handling of a malformed IEC 104 TCP packet in the Hitachi Energy MicroSCADA X SYS600, MicroSCADA Pro SYS600. Upon receiving a malformed IEC 104 TCP packet, the malformed packet is dropped, however the TCP connection is left open. This may cause a denial-of-service if the affected connection is left open. This issue affects: Hitachi Energy MicroSCADA Pro SYS600 version 9.4 FP2 Hotfix 4 and earlier versions Hitachi Energy MicroSCADA X SYS600 version 10 to version 10.3.1. cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.0:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.4:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3.1:*:*:*:*:*:*:*"
}
]
},
"generator": {
"engine": "Vulnogram 0.0.9"
},
"impact": {
"cvss": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "LOW",
"baseScore": 5.3,
"baseSeverity": "MEDIUM",
"confidentialityImpact": "NONE",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L",
"version": "3.1"
}
},
"problemtype": {
"problemtype_data": [
{
"description": [
{
"lang": "eng",
"value": "CWE-20 Improper Input Validation"
}
]
}
]
},
"references": {
"reference_data": [
{
"name": "https://search.abb.com/library/Download.aspx?DocumentID=8DBD000106&LanguageCode=en&DocumentPartId=&Action=Launch",
"refsource": "CONFIRM",
"url": "https://search.abb.com/library/Download.aspx?DocumentID=8DBD000106&LanguageCode=en&DocumentPartId=&Action=Launch"
}
]
},
"solution": [
{
"lang": "eng",
"value": "Remediated in SYS600 10.4 \nFor MicroSCADA Pro SYS600 - Upgrade to at least SYS600 version 10.4.\nFor MicroSCADA X SYS600 - Update to at least SYS600 version 10.4."
}
],
"source": {
"discovery": "INTERNAL"
},
"work_around": [
{
"lang": "eng",
"value": "Apply general mitigation factors as specify in the advisory."
}
]
}