cvelist/2020/15xxx/CVE-2020-15782.json
2021-09-14 11:01:02 +00:00

162 lines
7.6 KiB
JSON

{
"CVE_data_meta": {
"ASSIGNER": "productcert@siemens.com",
"ID": "CVE-2020-15782",
"STATE": "PUBLIC"
},
"data_format": "MITRE",
"data_version": "4.0",
"data_type": "CVE",
"affects": {
"vendor": {
"vendor_data": [
{
"vendor_name": "Siemens",
"product": {
"product_data": [
{
"product_name": "SIMATIC Drive Controller family",
"version": {
"version_data": [
{
"version_value": "All versions < V2.9.2"
}
]
}
},
{
"product_name": "SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants)",
"version": {
"version_data": [
{
"version_value": "All versions"
}
]
}
},
{
"product_name": "SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants)",
"version": {
"version_data": [
{
"version_value": "All versions < V21.9"
}
]
}
},
{
"product_name": "SIMATIC S7-1200 CPU family (incl. SIPLUS variants)",
"version": {
"version_data": [
{
"version_value": "All versions < V4.5.0"
}
]
}
},
{
"product_name": "SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants)",
"version": {
"version_data": [
{
"version_value": "All versions < V2.9.2"
}
]
}
},
{
"product_name": "SIMATIC S7-1500 Software Controller",
"version": {
"version_data": [
{
"version_value": "All versions < V21.9"
}
]
}
},
{
"product_name": "SIMATIC S7-PLCSIM Advanced",
"version": {
"version_data": [
{
"version_value": "All versions < V4.0"
}
]
}
},
{
"product_name": "SINAMICS PERFECT HARMONY GH180 Drives",
"version": {
"version_data": [
{
"version_value": "Drives manufactured before 2021-08-13"
}
]
}
},
{
"product_name": "SINUMERIK MC",
"version": {
"version_data": [
{
"version_value": "All versions < V6.15"
}
]
}
},
{
"product_name": "SINUMERIK ONE",
"version": {
"version_data": [
{
"version_value": "All versions < V6.15"
}
]
}
}
]
}
}
]
}
},
"problemtype": {
"problemtype_data": [
{
"description": [
{
"lang": "eng",
"value": "CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer"
}
]
}
]
},
"description": {
"description_data": [
{
"lang": "eng",
"value": "A vulnerability has been identified in SIMATIC Drive Controller family (All versions < V2.9.2), SIMATIC ET 200SP Open Controller CPU 1515SP PC (incl. SIPLUS variants) (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions < V21.9), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions < V4.5.0), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V2.9.2), SIMATIC S7-1500 Software Controller (All versions < V21.9), SIMATIC S7-PLCSIM Advanced (All versions < V4.0), SINAMICS PERFECT HARMONY GH180 Drives (Drives manufactured before 2021-08-13), SINUMERIK MC (All versions < V6.15), SINUMERIK ONE (All versions < V6.15). Affected devices are vulnerable to a memory protection bypass through a specific operation. A remote unauthenticated attacker with network access to port 102/tcp could potentially write arbitrary data and code to protected memory areas or read sensitive data to launch further attacks."
}
]
},
"references": {
"reference_data": [
{
"refsource": "MISC",
"url": "https://cert-portal.siemens.com/productcert/pdf/ssa-434534.pdf",
"name": "https://cert-portal.siemens.com/productcert/pdf/ssa-434534.pdf"
},
{
"refsource": "MISC",
"url": "https://cert-portal.siemens.com/productcert/pdf/ssa-434536.pdf",
"name": "https://cert-portal.siemens.com/productcert/pdf/ssa-434536.pdf"
},
{
"refsource": "MISC",
"url": "https://cert-portal.siemens.com/productcert/pdf/ssa-434535.pdf",
"name": "https://cert-portal.siemens.com/productcert/pdf/ssa-434535.pdf"
}
]
}
}