"CVE_data_meta": {
"ASSIGNER": "cve@mitre.org",
"ID": "CVE-2022-30319",
"STATE": "PUBLIC"
},
"affects": {
"vendor": {
"vendor_data": [
{
"product": {
"product_data": [
{
"product_name": "n/a",
"version": {
"version_data": [
{
"version_value": "n/a"
}
]
}
}
]
},
"vendor_name": "n/a"
}
]
}
},
"data_format": "MITRE",
"data_type": "CVE",
"data_version": "4.0",
"description": {
"description_data": [
{
"lang": "eng",
"value": "Saia Burgess Controls (SBC) PCD through 2022-05-06 allows Authentication bypass. According to FSCT-2022-0062, there is a Saia Burgess Controls (SBC) PCD S-Bus authentication bypass issue. The affected components are characterized as: S-Bus (5050/UDP) authentication. The potential impact is: Authentication bypass. The Saia Burgess Controls (SBC) PCD controllers utilize the S-Bus protocol (5050/UDP) for a variety of engineering purposes. It is possible to configure a password in order to restrict access to sensitive engineering functionality. Authentication functions on the basis of a MAC/IP whitelist with inactivity timeout to which an authenticated client's MAC/IP is stored. UDP traffic can be spoofed to bypass the whitelist-based access control. Since UDP is stateless, an attacker capable of passively observing traffic can spoof arbitrary messages using the MAC/IP of an authenticated client. This allows the attacker access to sensitive engineering functionality such as uploading/downloading control logic and manipulating controller configuration."
}
]
},
"problemtype": {
"problemtype_data": [
{
"description": [
{
"lang": "eng",
"value": "n/a"
}
]
}
]
},
"references": {
"reference_data": [
{
"url": "https://www.forescout.com/blog/",
"refsource": "MISC",
"name": "https://www.forescout.com/blog/"
},
{
"refsource": "MISC",
"name": "https://www.cisa.gov/uscert/ics/advisories/icsa-22-207-03",
"url": "https://www.cisa.gov/uscert/ics/advisories/icsa-22-207-03"
}
]
}
}