"data_version": "4.0",
"data_type": "CVE",
"data_format": "MITRE",
"CVE_data_meta": {
"ID": "CVE-2024-7515",
"ASSIGNER": "PSIRT@rockwellautomation.com",
"STATE": "PUBLIC"
},
"description": {
"description_data": [
{
"lang": "eng",
"value": "CVE-2024-7515 IMPACT\n\nA denial-of-service vulnerability exists in the affected products. A malformed PTP management packet can cause a major nonrecoverable fault in the controller."
}
]
},
"problemtype": {
"problemtype_data": [
{
"description": [
{
"lang": "eng",
"value": "CWE-20 Improper Input Validation",
"cweId": "CWE-20"
}
]
}
]
},
"affects": {
"vendor": {
"vendor_data": [
{
"vendor_name": "Rockwell Automation",
"product": {
"product_data": [
{
"product_name": "CompactLogix 5380 (5069-L3z)",
"version": {
"version_data": [
{
"version_affected": "=",
"version_value": "28.011"
}
]
}
},
{
"product_name": "ControlLogix\u00ae 5580 (1756- L8z)",
"version": {
"version_data": [
{
"version_affected": "=",
"version_value": "28.011"
}
]
}
},
{
"product_name": "GuardLogix 5580 (1756- L8zS)",
"version": {
"version_data": [
{
"version_affected": "=",
"version_value": "28.011"
}
]
}
},
{
"product_name": "Compact GuardLogix 5380 (5069 \u2013 L3zS2)",
"version": {
"version_data": [
{
"version_affected": "=",
"version_value": "28.011"
}
]
}
},
{
"product_name": "CompactLogix 5480 (5069-L4)",
"version": {
"version_data": [
{
"version_affected": "=",
"version_value": "28.011"
}
]
}
}
]
}
}
]
}
},
"references": {
"reference_data": [
{
"url": "https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD%201686.html",
"refsource": "MISC",
"name": "https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD%201686.html"
}
]
},
"generator": {
"engine": "Vulnogram 0.2.0"
},
"source": {
"discovery": "INTERNAL"
},
"work_around": [
{
"lang": "en",
"supportingMedia": [
{
"base64": false,
"type": "text/html",
"value": "<p>If PTP messages are not used, block at the network level, port UDP 319/320</p>"
}
],
"value": "If PTP messages are not used, block at the network level, port UDP 319/320"
}
],
"solution": [
{
"lang": "en",
"supportingMedia": [
{
"base64": false,
"type": "text/html",
"value": "Upgrade to:&nbsp;\n\n<span style=\"background-color: rgb(255, 255, 255);\">v36.011, v35.013, v34.014</span>"
}
],
"value": "Upgrade to:\u00a0\n\nv36.011, v35.013, v34.014"
}
]
}