"data_version": "4.0",
"data_type": "CVE",
"data_format": "MITRE",
"CVE_data_meta": {
"ID": "CVE-2020-28388",
"ASSIGNER": "productcert@siemens.com",
"STATE": "PUBLIC"
},
"description": {
"description_data": [
{
"lang": "eng",
"value": "A vulnerability has been identified in APOGEE PXC Compact (BACnet) (All versions < V3.5.5), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.20), APOGEE PXC Modular (BACnet) (All versions < V3.5.5), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.20), Nucleus NET (All versions < V5.2), Nucleus ReadyStart V3 (All versions < V2012.12), Nucleus Source Code (All versions), PLUSCONTROL 1st Gen (All versions), TALON TC Compact (BACnet) (All versions < V3.5.5), TALON TC Modular (BACnet) (All versions < V3.5.5). Initial Sequence Numbers (ISNs) for TCP connections are derived from an insufficiently random source. As a result, the ISN of current and future TCP connections could be predictable. An attacker could hijack existing sessions or spoof future ones."
}
]
},
"problemtype": {
"problemtype_data": [
{
"description": [
{
"lang": "eng",
"value": "CWE-342: Predictable Exact Value from Previous Values",
"cweId": "CWE-342"
}
]
}
]
},
"affects": {
"vendor": {
"vendor_data": [
{
"vendor_name": "Siemens",
"product": {
"product_data": [
{
"product_name": "APOGEE PXC Compact (BACnet)",
"version": {
"version_data": [
{
"version_affected": "=",
"version_value": "All versions < V3.5.5"
}
]
}
},
{
"product_name": "APOGEE PXC Compact (P2 Ethernet)",
"version": {
"version_data": [
{
"version_affected": "=",
"version_value": "All versions < V2.8.20"
}
]
}
},
{
"product_name": "APOGEE PXC Modular (BACnet)",
"version": {
"version_data": [
{
"version_affected": "=",
"version_value": "All versions < V3.5.5"
}
]
}
},
{
"product_name": "APOGEE PXC Modular (P2 Ethernet)",
"version": {
"version_data": [
{
"version_affected": "=",
"version_value": "All versions < V2.8.20"
}
]
}
},
{
"product_name": "Nucleus NET",
"version": {
"version_data": [
{
"version_affected": "=",
"version_value": "All versions < V5.2"
}
]
}
},
{
"product_name": "Nucleus ReadyStart V3",
"version": {
"version_data": [
{
"version_affected": "=",
"version_value": "All versions < V2012.12"
}
]
}
},
{
"product_name": "Nucleus Source Code",
"version": {
"version_data": [
{
"version_affected": "=",
"version_value": "All versions"
}
]
}
},
{
"product_name": "PLUSCONTROL 1st Gen",
"version": {
"version_data": [
{
"version_affected": "=",
"version_value": "All versions"
}
]
}
},
{
"product_name": "TALON TC Compact (BACnet)",
"version": {
"version_data": [
{
"version_affected": "=",
"version_value": "All versions < V3.5.5"
}
]
}
},
{
"product_name": "TALON TC Modular (BACnet)",
"version": {
"version_data": [
{
"version_affected": "=",
"version_value": "All versions < V3.5.5"
}
]
}
}
]
}
}
]
}
},
"references": {
"reference_data": [
{
"url": "https://cert-portal.siemens.com/productcert/pdf/ssa-362164.pdf",
"refsource": "MISC",
"name": "https://cert-portal.siemens.com/productcert/pdf/ssa-362164.pdf"
},
{
"url": "https://cert-portal.siemens.com/productcert/pdf/ssa-344238.pdf",
"refsource": "MISC",
"name": "https://cert-portal.siemens.com/productcert/pdf/ssa-344238.pdf"
},
{
"url": "https://cert-portal.siemens.com/productcert/pdf/ssa-436469.pdf",
"refsource": "MISC",
"name": "https://cert-portal.siemens.com/productcert/pdf/ssa-436469.pdf"
},
{
"url": "https://cert-portal.siemens.com/productcert/pdf/ssa-180579.pdf",
"refsource": "MISC",
"name": "https://cert-portal.siemens.com/productcert/pdf/ssa-180579.pdf"
}
]
},
"impact": {
"cvss": [
{
"version": "3.1",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:L/E:P/RL:O/RC:C",
"baseScore": 6.5,
"baseSeverity": "MEDIUM"
}
]
}
}