"CVE_data_meta": {
|
|
"ASSIGNER": "productcert@siemens.com",
|
|
"ID": "CVE-2019-18336",
|
|
"STATE": "PUBLIC"
|
|
},
|
|
"data_format": "MITRE",
|
|
"data_version": "4.0",
|
|
"data_type": "CVE",
|
|
"affects": {
|
|
"vendor": {
|
|
"vendor_data": [
|
|
{
|
|
"vendor_name": "Siemens AG",
|
|
"product": {
|
|
"product_data": [
|
|
{
|
|
"product_name": "SIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants)",
|
|
"version": {
|
|
"version_data": [
|
|
{
|
|
"version_value": "All versions < V3.X.17"
|
|
}
|
|
]
|
|
}
|
|
},
|
|
{
|
|
"product_name": "SIMATIC TDC CP51M1",
|
|
"version": {
|
|
"version_data": [
|
|
{
|
|
"version_value": "All versions < V1.1.8"
|
|
}
|
|
]
|
|
}
|
|
},
|
|
{
|
|
"product_name": "SIMATIC TDC CPU555",
|
|
"version": {
|
|
"version_data": [
|
|
{
|
|
"version_value": "All versions < V1.1.1"
|
|
}
|
|
]
|
|
}
|
|
},
|
|
{
|
|
"product_name": "SINUMERIK 840D sl",
|
|
"version": {
|
|
"version_data": [
|
|
{
|
|
"version_value": "All versions < V4.8.6"
|
|
}
|
|
]
|
|
}
|
|
},
|
|
{
|
|
"product_name": "SINUMERIK 840D sl",
|
|
"version": {
|
|
"version_data": [
|
|
{
|
|
"version_value": "All versions < V4.94"
|
|
}
|
|
]
|
|
}
|
|
}
|
|
]
|
|
}
|
|
}
|
|
]
|
|
}
|
|
},
|
|
"problemtype": {
|
|
"problemtype_data": [
|
|
{
|
|
"description": [
|
|
{
|
|
"lang": "eng",
|
|
"value": "CWE-400: Uncontrolled Resource Consumption"
|
|
}
|
|
]
|
|
}
|
|
]
|
|
},
|
|
"description": {
|
|
"description_data": [
|
|
{
|
|
"lang": "eng",
|
|
"value": "A vulnerability has been identified in SIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions < V3.X.17), SIMATIC TDC CP51M1 (All versions < V1.1.8), SIMATIC TDC CPU555 (All versions < V1.1.1), SINUMERIK 840D sl (All versions < V4.8.6), SINUMERIK 840D sl (All versions < V4.94). Specially crafted packets sent to port 102/tcp (Profinet) could cause the affected device to go into defect mode. A restart is required in order to recover the system. Successful exploitation requires an attacker to have network access to port 102/tcp, with no authentication. No user interation is required. At the time of advisory publication no public exploitation of this security vulnerability was known."
|
|
}
|
|
]
|
|
},
|
|
"references": {
|
|
"reference_data": [
|
|
{
|
|
"refsource": "MISC",
|
|
"url": "https://cert-portal.siemens.com/productcert/pdf/ssa-508982.pdf",
|
|
"name": "https://cert-portal.siemens.com/productcert/pdf/ssa-508982.pdf"
|
|
}
|
|
]
|
|
}
|
|
} |