"data_version": "4.0",
"data_type": "CVE",
"data_format": "MITRE",
"CVE_data_meta": {
"ID": "CVE-2024-6089",
"ASSIGNER": "PSIRT@rockwellautomation.com",
"STATE": "PUBLIC"
},
"description": {
"description_data": [
{
"lang": "eng",
"value": "An input validation vulnerability exists in the Rockwell Automation\u00a05015 - AENFTXT\u00a0when a manipulated PTP packet is sent, causing the secondary adapter to result in a major nonrecoverable fault. If exploited, a power cycle is required to recover the product."
}
]
},
"problemtype": {
"problemtype_data": [
{
"description": [
{
"lang": "eng",
"value": "CWE-20: Improper Input Validation",
"cweId": "CWE-20"
}
]
}
]
},
"affects": {
"vendor": {
"vendor_data": [
{
"vendor_name": "Rockwell Automation",
"product": {
"product_data": [
{
"product_name": "5015 - AENFTXT",
"version": {
"version_data": [
{
"version_affected": "=",
"version_value": "v2.011"
}
]
}
}
]
}
}
]
}
},
"references": {
"reference_data": [
{
"url": "https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1680.html",
"refsource": "MISC",
"name": "https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1680.html"
}
]
},
"generator": {
"engine": "Vulnogram 0.2.0"
},
"source": {
"advisory": "SD1680",
"discovery": "INTERNAL"
},
"solution": [
{
"lang": "en",
"supportingMedia": [
{
"base64": false,
"type": "text/html",
"value": "\n\n<p>Customers using the affected software are encouraged to apply the risk mitigations, if possible.</p><ul><li><p>Update to the corrected firmware revision, v2.012.</p></li></ul><ul><li><p>For information on how to mitigate Security Risks on industrial automation control systems, we encourage customers to implement our suggested <a target=\"_blank\" rel=\"nofollow\" href=\"https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight\">security best practices</a>&nbsp;to minimize the risk of the vulnerability.</p></li></ul>"
}
],
"value": "Customers using the affected software are encouraged to apply the risk mitigations, if possible.\n\n * Update to the corrected firmware revision, v2.012.\n\n\n\n\n * For information on how to mitigate Security Risks on industrial automation control systems, we encourage customers to implement our suggested security best practices https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1085012/loc/en_US#__highlight \u00a0to minimize the risk of the vulnerability."
}
]
}