cvelist/2024/21xxx/CVE-2024-21916.json
2024-01-31 19:00:32 +00:00

123 lines
5.3 KiB
JSON

{
"data_version": "4.0",
"data_type": "CVE",
"data_format": "MITRE",
"CVE_data_meta": {
"ID": "CVE-2024-21916",
"ASSIGNER": "PSIRT@rockwellautomation.com",
"STATE": "PUBLIC"
},
"description": {
"description_data": [
{
"lang": "eng",
"value": "\nA denial-of-service vulnerability exists in specific Rockwell Automation ControlLogix ang GuardLogix controllers. If exploited, the product could potentially experience a major nonrecoverable fault (MNRF). The device will restart itself to recover from the MNRF."
}
]
},
"problemtype": {
"problemtype_data": [
{
"description": [
{
"lang": "eng",
"value": "CWE-119 Improper Restriction of Operations within the Bounds of a Memory Buffer",
"cweId": "CWE-119"
}
]
}
]
},
"affects": {
"vendor": {
"vendor_data": [
{
"vendor_name": "Rockwell Automation",
"product": {
"product_data": [
{
"product_name": "ControlLogix\u00ae 5570",
"version": {
"version_data": [
{
"version_affected": "=",
"version_value": "20.011"
}
]
}
},
{
"product_name": "GuardLogix\u00ae 5570",
"version": {
"version_data": [
{
"version_affected": "=",
"version_value": "20.011"
}
]
}
},
{
"product_name": "ControlLogix\u00ae 5570 redundant",
"version": {
"version_data": [
{
"version_affected": "=",
"version_value": "20.054_kit1"
}
]
}
}
]
}
}
]
}
},
"references": {
"reference_data": [
{
"url": "https://www.rockwellautomation.com/en-us/support/advisory.SD1661.html",
"refsource": "MISC",
"name": "https://www.rockwellautomation.com/en-us/support/advisory.SD1661.html"
}
]
},
"generator": {
"engine": "Vulnogram 0.1.0-dev"
},
"source": {
"discovery": "UNKNOWN"
},
"solution": [
{
"lang": "en",
"supportingMedia": [
{
"base64": false,
"type": "text/html",
"value": "\n\n<ul><li>Update to corrected Firmware.&nbsp;</li></ul>\n\n<table><tbody><tr><td><p><a target=\"_blank\" rel=\"nofollow\">Affected Product</a></p></td><td><p><a target=\"_blank\" rel=\"nofollow\">First Known in Firmware</a></p></td><td><p>Corrected in Firmware</p></td></tr><tr><td><p>ControlLogix\u00ae 5570</p></td><td><p>20.011</p></td><td><p>v33.016, 34.013, 35.012, 36.011 and later</p></td></tr><tr><td><p>GuardLogix\u00ae 5570<b></b></p></td><td><p>20.011</p></td><td><p>v33.016, 34.013, 35.012, 36.011 and later</p></td></tr><tr><td><p>ControlLogix\u00ae 5570 redundant<b></b></p></td><td><p>20.054_kit1</p></td><td><p>v33.053_kit1, 34.052_kit1, 35.052_kit1, 36.051_kit1 and late</p></td></tr></tbody></table>\n\n<br>\n\n"
}
],
"value": "\n * Update to corrected Firmware.\u00a0\n\n\n\n\nAffected Product\n\nFirst Known in Firmware\n\nCorrected in Firmware\n\nControlLogix\u00ae 5570\n\n20.011\n\nv33.016, 34.013, 35.012, 36.011 and later\n\nGuardLogix\u00ae 5570\n\n20.011\n\nv33.016, 34.013, 35.012, 36.011 and later\n\nControlLogix\u00ae 5570 redundant\n\n20.054_kit1\n\nv33.053_kit1, 34.052_kit1, 35.052_kit1, 36.051_kit1 and late\n\n\n\n\n\n\n"
}
],
"impact": {
"cvss": [
{
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 8.6,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "CHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H",
"version": "3.1"
}
]
}
}