"id": "CVE-2022-2502",
"sourceIdentifier": "cybersecurity@hitachienergy.com",
"published": "2023-07-26T06:15:09.760",
"lastModified": "2023-07-26T12:53:08.817",
"vulnStatus": "Awaiting Analysis",
"descriptions": [
{
"lang": "en",
"value": "A vulnerability exists in the HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-5 and the CMU contains the license feature \u2018Advanced security\u2019 which must be ordered separately. If these preconditions are fulfilled, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the targeted RTU500 CMU to reboot. The vulnerability is caused by a missing input data validation which eventually if exploited causes an internal buffer to overflow in the HCI IEC 60870-5-104 function."
}
],
"metrics": {
"cvssMetricV31": [
{
"source": "cybersecurity@hitachienergy.com",
"type": "Secondary",
"cvssData": {
"version": "3.1",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"attackVector": "NETWORK",
"attackComplexity": "LOW",
"privilegesRequired": "NONE",
"userInteraction": "NONE",
"scope": "UNCHANGED",
"confidentialityImpact": "NONE",
"integrityImpact": "NONE",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH"
},
"exploitabilityScore": 3.9,
"impactScore": 3.6
}
]
},
"weaknesses": [
{
"source": "cybersecurity@hitachienergy.com",
"type": "Secondary",
"description": [
{
"lang": "en",
"value": "CWE-120"
}
]
}
],
"references": [
{
"url": "https://search.abb.com/library/Download.aspx?DocumentID=8DBD000121&LanguageCode=en&DocumentPartId=&Action=Launch",
"source": "cybersecurity@hitachienergy.com"
}
]
}