{ "id": "CVE-2024-1573", "sourceIdentifier": "Mitsubishielectric.Psirt@yd.MitsubishiElectric.co.jp", "published": "2024-07-04T09:15:03.260", "lastModified": "2024-07-05T12:55:51.367", "vulnStatus": "Awaiting Analysis", "cveTags": [], "descriptions": [ { "lang": "en", "value": "Improper Authentication vulnerability in the mobile monitoring feature of ICONICS GENESIS64 versions 10.97 to 10.97.2, Mitsubishi Electric GENESIS64 versions 10.97 to 10.97.2 and Mitsubishi Electric MC Works64 all versions allows a remote unauthenticated attacker to bypass proper authentication and log in to the system when all of the following conditions are met: * Active Directory is used in the security setting.\n * \u201cAutomatic log in\u201d option is enabled in the security setting.\n * The IcoAnyGlass IIS Application Pool is running under an Active Directory Domain Account.\n * The IcoAnyGlass IIS Application Pool account is included in GENESIS64TM and MC Works64 Security and has permission to log in." }, { "lang": "es", "value": "Vulnerabilidad de autenticaci\u00f3n incorrecta en la funci\u00f3n de monitoreo m\u00f3vil de ICONICS GENESIS64 versiones 10.97 a 10.97.2, Mitsubishi Electric GENESIS64 versiones 10.97 a 10.97.2 y Mitsubishi Electric MC Works64 todas las versiones permite que un atacante remoto no autenticado omita la autenticaci\u00f3n adecuada e inicie sesi\u00f3n en el sistema cuando Se cumplen todas las condiciones siguientes: * Se utiliza Active Directory en la configuraci\u00f3n de seguridad. * La opci\u00f3n \"Inicio de sesi\u00f3n autom\u00e1tico\" est\u00e1 habilitada en la configuraci\u00f3n de seguridad. * El grupo de aplicaciones IcoAnyGlass IIS se ejecuta en una cuenta de dominio de Active Directory. * La cuenta del grupo de aplicaciones IcoAnyGlass IIS est\u00e1 incluida en GENESIS64TM y MC Works64 Security y tiene permiso para iniciar sesi\u00f3n." } ], "metrics": { "cvssMetricV31": [ { "source": "Mitsubishielectric.Psirt@yd.MitsubishiElectric.co.jp", "type": "Secondary", "cvssData": { "version": "3.1", "vectorString": "CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:H/A:N", "attackVector": "NETWORK", "attackComplexity": "HIGH", "privilegesRequired": "NONE", "userInteraction": "NONE", "scope": "UNCHANGED", "confidentialityImpact": "NONE", "integrityImpact": "HIGH", "availabilityImpact": "NONE", "baseScore": 5.9, "baseSeverity": "MEDIUM" }, "exploitabilityScore": 2.2, "impactScore": 3.6 } ] }, "weaknesses": [ { "source": "Mitsubishielectric.Psirt@yd.MitsubishiElectric.co.jp", "type": "Primary", "description": [ { "lang": "en", "value": "CWE-287" } ] } ], "references": [ { "url": "https://jvn.jp/vu/JVNVU98894016/", "source": "Mitsubishielectric.Psirt@yd.MitsubishiElectric.co.jp" }, { "url": "https://www.cisa.gov/news-events/ics-advisories/icsa-24-184-03", "source": "Mitsubishielectric.Psirt@yd.MitsubishiElectric.co.jp" }, { "url": "https://www.mitsubishielectric.com/en/psirt/vulnerability/pdf/2024-004_en.pdf", "source": "Mitsubishielectric.Psirt@yd.MitsubishiElectric.co.jp" } ] }