{ "id": "CVE-2024-44102", "sourceIdentifier": "productcert@siemens.com", "published": "2024-11-12T13:15:08.203", "lastModified": "2024-11-12T13:55:21.227", "vulnStatus": "Undergoing Analysis", "cveTags": [], "descriptions": [ { "lang": "en", "value": "A vulnerability has been identified in PP TeleControl Server Basic 1000 to 5000 V3.1 (6NH9910-0AA31-0AE1) (All versions < V3.1.2.1 with redundancy configured), PP TeleControl Server Basic 256 to 1000 V3.1 (6NH9910-0AA31-0AD1) (All versions < V3.1.2.1 with redundancy configured), PP TeleControl Server Basic 32 to 64 V3.1 (6NH9910-0AA31-0AF1) (All versions < V3.1.2.1 with redundancy configured), PP TeleControl Server Basic 64 to 256 V3.1 (6NH9910-0AA31-0AC1) (All versions < V3.1.2.1 with redundancy configured), PP TeleControl Server Basic 8 to 32 V3.1 (6NH9910-0AA31-0AB1) (All versions < V3.1.2.1 with redundancy configured), TeleControl Server Basic 1000 V3.1 (6NH9910-0AA31-0AD0) (All versions < V3.1.2.1 with redundancy configured), TeleControl Server Basic 256 V3.1 (6NH9910-0AA31-0AC0) (All versions < V3.1.2.1 with redundancy configured), TeleControl Server Basic 32 V3.1 (6NH9910-0AA31-0AF0) (All versions < V3.1.2.1 with redundancy configured), TeleControl Server Basic 5000 V3.1 (6NH9910-0AA31-0AE0) (All versions < V3.1.2.1 with redundancy configured), TeleControl Server Basic 64 V3.1 (6NH9910-0AA31-0AB0) (All versions < V3.1.2.1 with redundancy configured), TeleControl Server Basic 8 V3.1 (6NH9910-0AA31-0AA0) (All versions < V3.1.2.1 with redundancy configured), TeleControl Server Basic Serv Upgr (6NH9910-0AA31-0GA1) (All versions < V3.1.2.1 with redundancy configured), TeleControl Server Basic Upgr V3.1 (6NH9910-0AA31-0GA0) (All versions < V3.1.2.1 with redundancy configured). The affected system allows remote users to send maliciously crafted objects. Due to insecure deserialization of user-supplied content by the affected software, an unauthenticated attacker could exploit this vulnerability by sending a maliciously crafted serialized object. This could allow the attacker to execute arbitrary code on the device with SYSTEM privileges." } ], "metrics": { "cvssMetricV40": [ { "source": "productcert@siemens.com", "type": "Secondary", "cvssData": { "version": "4.0", "vectorString": "CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:H/SI:H/SA:H/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X", "attackVector": "NETWORK", "attackComplexity": "LOW", "attackRequirements": "NONE", "privilegesRequired": "NONE", "userInteraction": "NONE", "vulnerableSystemConfidentiality": "HIGH", "vulnerableSystemIntegrity": "HIGH", "vulnerableSystemAvailability": "HIGH", "subsequentSystemConfidentiality": "HIGH", "subsequentSystemIntegrity": "HIGH", "subsequentSystemAvailability": "HIGH", "exploitMaturity": "NOT_DEFINED", "confidentialityRequirements": "NOT_DEFINED", "integrityRequirements": "NOT_DEFINED", "availabilityRequirements": "NOT_DEFINED", "modifiedAttackVector": "NOT_DEFINED", "modifiedAttackComplexity": "NOT_DEFINED", "modifiedAttackRequirements": "NOT_DEFINED", "modifiedPrivilegesRequired": "NOT_DEFINED", "modifiedUserInteraction": "NOT_DEFINED", "modifiedVulnerableSystemConfidentiality": "NOT_DEFINED", "modifiedVulnerableSystemIntegrity": "NOT_DEFINED", "modifiedVulnerableSystemAvailability": "NOT_DEFINED", "modifiedSubsequentSystemConfidentiality": "NOT_DEFINED", "modifiedSubsequentSystemIntegrity": "NOT_DEFINED", "modifiedSubsequentSystemAvailability": "NOT_DEFINED", "safety": "NOT_DEFINED", "automatable": "NOT_DEFINED", "recovery": "NOT_DEFINED", "valueDensity": "NOT_DEFINED", "vulnerabilityResponseEffort": "NOT_DEFINED", "providerUrgency": "NOT_DEFINED", "baseScore": 10.0, "baseSeverity": "CRITICAL" } } ], "cvssMetricV31": [ { "source": "productcert@siemens.com", "type": "Primary", "cvssData": { "version": "3.1", "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H", "attackVector": "NETWORK", "attackComplexity": "LOW", "privilegesRequired": "NONE", "userInteraction": "NONE", "scope": "CHANGED", "confidentialityImpact": "HIGH", "integrityImpact": "HIGH", "availabilityImpact": "HIGH", "baseScore": 10.0, "baseSeverity": "CRITICAL" }, "exploitabilityScore": 3.9, "impactScore": 6.0 } ] }, "weaknesses": [ { "source": "productcert@siemens.com", "type": "Primary", "description": [ { "lang": "en", "value": "CWE-502" } ] } ], "references": [ { "url": "https://cert-portal.siemens.com/productcert/html/ssa-454789.html", "source": "productcert@siemens.com" } ] }