"id": "CVE-2020-6967",
|
|
"sourceIdentifier": "ics-cert@hq.dhs.gov",
|
|
"published": "2020-03-23T21:15:12.207",
|
|
"lastModified": "2020-03-27T17:40:42.710",
|
|
"vulnStatus": "Analyzed",
|
|
"descriptions": [
|
|
{
|
|
"lang": "en",
|
|
"value": "In Rockwell Automation all versions of FactoryTalk Diagnostics software, a subsystem of the FactoryTalk Services Platform, FactoryTalk Diagnostics exposes a .NET Remoting endpoint via RNADiagnosticsSrv.exe at TCPtcp/8082, which can insecurely deserialize untrusted data."
|
|
},
|
|
{
|
|
"lang": "es",
|
|
"value": "En Rockwell Automation, todas las versiones del software FactoryTalk Diagnostics, un subsistema de la FactoryTalk Services Platform, FactoryTalk Diagnostics expone un endpoint .NET Remoting por medio del archivo RNADiagnosticsSrv.exe en TCPtcp/8082, lo cual puede deserializar de forma no segura los datos no confiables."
|
|
}
|
|
],
|
|
"metrics": {
|
|
"cvssMetricV31": [
|
|
{
|
|
"source": "nvd@nist.gov",
|
|
"type": "Primary",
|
|
"cvssData": {
|
|
"version": "3.1",
|
|
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
|
|
"attackVector": "NETWORK",
|
|
"attackComplexity": "LOW",
|
|
"privilegesRequired": "NONE",
|
|
"userInteraction": "NONE",
|
|
"scope": "UNCHANGED",
|
|
"confidentialityImpact": "HIGH",
|
|
"integrityImpact": "HIGH",
|
|
"availabilityImpact": "HIGH",
|
|
"baseScore": 9.8,
|
|
"baseSeverity": "CRITICAL"
|
|
},
|
|
"exploitabilityScore": 3.9,
|
|
"impactScore": 5.9
|
|
}
|
|
],
|
|
"cvssMetricV2": [
|
|
{
|
|
"source": "nvd@nist.gov",
|
|
"type": "Primary",
|
|
"cvssData": {
|
|
"version": "2.0",
|
|
"vectorString": "AV:N/AC:L/Au:N/C:C/I:C/A:C",
|
|
"accessVector": "NETWORK",
|
|
"accessComplexity": "LOW",
|
|
"authentication": "NONE",
|
|
"confidentialityImpact": "COMPLETE",
|
|
"integrityImpact": "COMPLETE",
|
|
"availabilityImpact": "COMPLETE",
|
|
"baseScore": 10.0
|
|
},
|
|
"baseSeverity": "HIGH",
|
|
"exploitabilityScore": 10.0,
|
|
"impactScore": 10.0,
|
|
"acInsufInfo": false,
|
|
"obtainAllPrivilege": false,
|
|
"obtainUserPrivilege": false,
|
|
"obtainOtherPrivilege": false,
|
|
"userInteractionRequired": false
|
|
}
|
|
]
|
|
},
|
|
"weaknesses": [
|
|
{
|
|
"source": "nvd@nist.gov",
|
|
"type": "Primary",
|
|
"description": [
|
|
{
|
|
"lang": "en",
|
|
"value": "CWE-502"
|
|
}
|
|
]
|
|
},
|
|
{
|
|
"source": "ics-cert@hq.dhs.gov",
|
|
"type": "Secondary",
|
|
"description": [
|
|
{
|
|
"lang": "en",
|
|
"value": "CWE-502"
|
|
}
|
|
]
|
|
}
|
|
],
|
|
"configurations": [
|
|
{
|
|
"nodes": [
|
|
{
|
|
"operator": "OR",
|
|
"negate": false,
|
|
"cpeMatch": [
|
|
{
|
|
"vulnerable": true,
|
|
"criteria": "cpe:2.3:a:rockwellautomation:factorytalk_services_platform:-:*:*:*:*:*:*:*",
|
|
"matchCriteriaId": "DD8A46F8-B6B4-4F58-AD35-3C9DACEA4F16"
|
|
}
|
|
]
|
|
}
|
|
]
|
|
}
|
|
],
|
|
"references": [
|
|
{
|
|
"url": "https://www.us-cert.gov/ics/advisories/icsa-20-051-02",
|
|
"source": "ics-cert@hq.dhs.gov",
|
|
"tags": [
|
|
"Third Party Advisory",
|
|
"US Government Resource"
|
|
]
|
|
}
|
|
]
|
|
} |