mirror of
https://github.com/fkie-cad/nvd-json-data-feeds.git
synced 2025-07-09 16:05:11 +00:00
150 lines
4.8 KiB
JSON
150 lines
4.8 KiB
JSON
{
|
|
"id": "CVE-2023-36380",
|
|
"sourceIdentifier": "productcert@siemens.com",
|
|
"published": "2023-10-10T11:15:11.817",
|
|
"lastModified": "2024-11-21T08:09:38.097",
|
|
"vulnStatus": "Modified",
|
|
"cveTags": [],
|
|
"descriptions": [
|
|
{
|
|
"lang": "en",
|
|
"value": "A vulnerability has been identified in CP-8031 MASTER MODULE (All versions < CPCI85 V05.11 (only with activated debug support)), CP-8050 MASTER MODULE (All versions < CPCI85 V05.11 (only with activated debug support)). The affected devices contain a hard-coded ID in the SSH `authorized_keys` configuration file. An attacker with knowledge of the corresponding private key could login to the device via SSH. Only devices with activated debug support are affected."
|
|
},
|
|
{
|
|
"lang": "es",
|
|
"value": "Se ha identificado una vulnerabilidad en: \nCP-8031 MASTER MODULE (Todas las versiones < CPCI85 V05.11 (solo con soporte de depuraci\u00f3n activado)), \nCP-8050 MASTER MODULE (Todas las versiones < CPCI85 V05.11 (solo con soporte de depuraci\u00f3n activado)). \nLos dispositivos afectados contienen una identificaci\u00f3n codificada en el archivo de configuraci\u00f3n SSH `authorized_keys`. Un atacante con conocimiento de la clave privada correspondiente podr\u00eda iniciar sesi\u00f3n en el dispositivo a trav\u00e9s de SSH. S\u00f3lo se ven afectados los dispositivos con soporte de depuraci\u00f3n activado."
|
|
}
|
|
],
|
|
"metrics": {
|
|
"cvssMetricV31": [
|
|
{
|
|
"source": "productcert@siemens.com",
|
|
"type": "Secondary",
|
|
"cvssData": {
|
|
"version": "3.1",
|
|
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
|
|
"baseScore": 9.8,
|
|
"baseSeverity": "CRITICAL",
|
|
"attackVector": "NETWORK",
|
|
"attackComplexity": "LOW",
|
|
"privilegesRequired": "NONE",
|
|
"userInteraction": "NONE",
|
|
"scope": "UNCHANGED",
|
|
"confidentialityImpact": "HIGH",
|
|
"integrityImpact": "HIGH",
|
|
"availabilityImpact": "HIGH"
|
|
},
|
|
"exploitabilityScore": 3.9,
|
|
"impactScore": 5.9
|
|
},
|
|
{
|
|
"source": "nvd@nist.gov",
|
|
"type": "Primary",
|
|
"cvssData": {
|
|
"version": "3.1",
|
|
"vectorString": "CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H",
|
|
"baseScore": 7.8,
|
|
"baseSeverity": "HIGH",
|
|
"attackVector": "LOCAL",
|
|
"attackComplexity": "LOW",
|
|
"privilegesRequired": "LOW",
|
|
"userInteraction": "NONE",
|
|
"scope": "UNCHANGED",
|
|
"confidentialityImpact": "HIGH",
|
|
"integrityImpact": "HIGH",
|
|
"availabilityImpact": "HIGH"
|
|
},
|
|
"exploitabilityScore": 1.8,
|
|
"impactScore": 5.9
|
|
}
|
|
]
|
|
},
|
|
"weaknesses": [
|
|
{
|
|
"source": "productcert@siemens.com",
|
|
"type": "Primary",
|
|
"description": [
|
|
{
|
|
"lang": "en",
|
|
"value": "CWE-798"
|
|
}
|
|
]
|
|
}
|
|
],
|
|
"configurations": [
|
|
{
|
|
"operator": "AND",
|
|
"nodes": [
|
|
{
|
|
"operator": "OR",
|
|
"negate": false,
|
|
"cpeMatch": [
|
|
{
|
|
"vulnerable": true,
|
|
"criteria": "cpe:2.3:o:siemens:cp-8050_firmware:*:*:*:*:cpci85:*:*:*",
|
|
"versionEndExcluding": "05.11",
|
|
"matchCriteriaId": "5DDCBDDD-3936-462A-A93A-696AAEBB4EBA"
|
|
}
|
|
]
|
|
},
|
|
{
|
|
"operator": "OR",
|
|
"negate": false,
|
|
"cpeMatch": [
|
|
{
|
|
"vulnerable": false,
|
|
"criteria": "cpe:2.3:h:siemens:cp-8050:-:*:*:*:*:*:*:*",
|
|
"matchCriteriaId": "929EF3DE-C8E6-49DA-98C0-13AB4C966AA7"
|
|
}
|
|
]
|
|
}
|
|
]
|
|
},
|
|
{
|
|
"operator": "AND",
|
|
"nodes": [
|
|
{
|
|
"operator": "OR",
|
|
"negate": false,
|
|
"cpeMatch": [
|
|
{
|
|
"vulnerable": true,
|
|
"criteria": "cpe:2.3:o:siemens:cp-8031_firmware:*:*:*:*:cpci85:*:*:*",
|
|
"versionEndExcluding": "05.11",
|
|
"matchCriteriaId": "36A1AC2A-A6D1-4C2F-9439-FA093EB6B44D"
|
|
}
|
|
]
|
|
},
|
|
{
|
|
"operator": "OR",
|
|
"negate": false,
|
|
"cpeMatch": [
|
|
{
|
|
"vulnerable": false,
|
|
"criteria": "cpe:2.3:h:siemens:cp-8031:-:*:*:*:*:*:*:*",
|
|
"matchCriteriaId": "D24F9EDC-DA14-477D-B9C1-C9BF56E9B057"
|
|
}
|
|
]
|
|
}
|
|
]
|
|
}
|
|
],
|
|
"references": [
|
|
{
|
|
"url": "https://cert-portal.siemens.com/productcert/pdf/ssa-134651.pdf",
|
|
"source": "productcert@siemens.com",
|
|
"tags": [
|
|
"Patch",
|
|
"Vendor Advisory"
|
|
]
|
|
},
|
|
{
|
|
"url": "https://cert-portal.siemens.com/productcert/pdf/ssa-134651.pdf",
|
|
"source": "af854a3a-2127-422b-91ae-364da2661108",
|
|
"tags": [
|
|
"Patch",
|
|
"Vendor Advisory"
|
|
]
|
|
}
|
|
]
|
|
} |