mirror of
https://github.com/fkie-cad/nvd-json-data-feeds.git
synced 2025-06-07 05:28:59 +00:00
80 lines
3.1 KiB
JSON
80 lines
3.1 KiB
JSON
{
|
|
"id": "CVE-2024-1182",
|
|
"sourceIdentifier": "Mitsubishielectric.Psirt@yd.MitsubishiElectric.co.jp",
|
|
"published": "2024-07-04T09:15:02.743",
|
|
"lastModified": "2024-11-21T08:49:58.813",
|
|
"vulnStatus": "Awaiting Analysis",
|
|
"cveTags": [],
|
|
"descriptions": [
|
|
{
|
|
"lang": "en",
|
|
"value": "Uncontrolled Search Path Element vulnerability in ICONICS GENESIS64 all versions, Mitsubishi Electric GENESIS64 all versions and Mitsubishi Electric MC Works64 all versions allows a local attacker to execute a malicious code by storing a specially crafted DLL in a specific folder when GENESIS64 and MC Works64 are installed with the Pager agent in the alarm multi-agent notification feature."
|
|
},
|
|
{
|
|
"lang": "es",
|
|
"value": "Vulnerabilidad no controlada del elemento de ruta de b\u00fasqueda en ICONICS GENESIS64 todas las versiones, Mitsubishi Electric GENESIS64 todas las versiones y Mitsubishi Electric MC Works64 todas las versiones permite a un atacante local ejecutar un c\u00f3digo malicioso almacenando una DLL especialmente manipulada en una carpeta espec\u00edfica cuando GENESIS64 y MC Works64 est\u00e1n instalados con el agente buscapersonas en la funci\u00f3n de notificaci\u00f3n de alarma de m\u00faltiples agentes."
|
|
}
|
|
],
|
|
"metrics": {
|
|
"cvssMetricV31": [
|
|
{
|
|
"source": "Mitsubishielectric.Psirt@yd.MitsubishiElectric.co.jp",
|
|
"type": "Secondary",
|
|
"cvssData": {
|
|
"version": "3.1",
|
|
"vectorString": "CVSS:3.1/AV:L/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:H",
|
|
"baseScore": 7.0,
|
|
"baseSeverity": "HIGH",
|
|
"attackVector": "LOCAL",
|
|
"attackComplexity": "HIGH",
|
|
"privilegesRequired": "LOW",
|
|
"userInteraction": "NONE",
|
|
"scope": "UNCHANGED",
|
|
"confidentialityImpact": "HIGH",
|
|
"integrityImpact": "HIGH",
|
|
"availabilityImpact": "HIGH"
|
|
},
|
|
"exploitabilityScore": 1.0,
|
|
"impactScore": 5.9
|
|
}
|
|
]
|
|
},
|
|
"weaknesses": [
|
|
{
|
|
"source": "Mitsubishielectric.Psirt@yd.MitsubishiElectric.co.jp",
|
|
"type": "Secondary",
|
|
"description": [
|
|
{
|
|
"lang": "en",
|
|
"value": "CWE-427"
|
|
}
|
|
]
|
|
}
|
|
],
|
|
"references": [
|
|
{
|
|
"url": "https://jvn.jp/vu/JVNVU98894016/",
|
|
"source": "Mitsubishielectric.Psirt@yd.MitsubishiElectric.co.jp"
|
|
},
|
|
{
|
|
"url": "https://www.cisa.gov/news-events/ics-advisories/icsa-24-184-03",
|
|
"source": "Mitsubishielectric.Psirt@yd.MitsubishiElectric.co.jp"
|
|
},
|
|
{
|
|
"url": "https://www.mitsubishielectric.com/en/psirt/vulnerability/pdf/2024-004_en.pdf",
|
|
"source": "Mitsubishielectric.Psirt@yd.MitsubishiElectric.co.jp"
|
|
},
|
|
{
|
|
"url": "https://jvn.jp/vu/JVNVU98894016/",
|
|
"source": "af854a3a-2127-422b-91ae-364da2661108"
|
|
},
|
|
{
|
|
"url": "https://www.cisa.gov/news-events/ics-advisories/icsa-24-184-03",
|
|
"source": "af854a3a-2127-422b-91ae-364da2661108"
|
|
},
|
|
{
|
|
"url": "https://www.mitsubishielectric.com/en/psirt/vulnerability/pdf/2024-004_en.pdf",
|
|
"source": "af854a3a-2127-422b-91ae-364da2661108"
|
|
}
|
|
]
|
|
} |