"id": "CVE-2011-4859",
"sourceIdentifier": "cve@mitre.org",
"published": "2011-12-17T11:55:11.917",
"lastModified": "2017-08-29T01:30:36.817",
"vulnStatus": "Modified",
"descriptions": [
{
"lang": "en",
"value": "The Schneider Electric Quantum Ethernet Module, as used in the Quantum 140NOE771* and 140CPU65* modules, the Premium TSXETY* and TSXP57* modules, the M340 BMXNOE01* and BMXP3420* modules, and the STB DIO STBNIC2212 and STBNIP2* modules, uses hardcoded passwords for the (1) AUTCSE, (2) AUT_CSE, (3) fdrusers, (4) ftpuser, (5) loader, (6) nic2212, (7) nimrohs2212, (8) nip2212, (9) noe77111_v500, (10) ntpupdate, (11) pcfactory, (12) sysdiag, (13) target, (14) test, (15) USER, and (16) webserver accounts, which makes it easier for remote attackers to obtain access via the (a) TELNET, (b) Windriver Debug, or (c) FTP port."
},
{
"lang": "es",
"value": "El m\u00f3dulo Schneider Electric Quantum Ethernet, tal como se utiliza en los m\u00f3dulos Quantum 140NOE771* y 140CPU65*, los m\u00f3dulos Premium TSXETY* y TSXP57*, los m\u00f3dulos M340 BMXNOE01* y BMXP3420*, y los m\u00f3dulos STB DIO STBNIC2212 y STBNIP2*, utiliza contrase\u00f1as est\u00e1ticas para las cuentas (1) AUTCSE, (2) AUT_CSE, (3) fdrusers, (4) ftpuser, (5) loader, (6) nic2212, (7) nimrohs2212, (8) nip2212, (9) noe77111_v500, (10) ntpupdate, (11) pcfactory, (12) sysdiag, (13) target, (14) test, (15) USER, y (16) webserver, lo que facilita a atacantes remotos obtener acceso a trav\u00e9s de (a) TELNET, (b) Windriver Debug, o (c) el puerto FTP."
}
],
"metrics": {
"cvssMetricV2": [
{
"source": "nvd@nist.gov",
"type": "Primary",
"cvssData": {
"version": "2.0",
"vectorString": "AV:N/AC:L/Au:N/C:C/I:C/A:C",
"accessVector": "NETWORK",
"accessComplexity": "LOW",
"authentication": "NONE",
"confidentialityImpact": "COMPLETE",
"integrityImpact": "COMPLETE",
"availabilityImpact": "COMPLETE",
"baseScore": 10.0
},
"baseSeverity": "HIGH",
"exploitabilityScore": 10.0,
"impactScore": 10.0,
"acInsufInfo": false,
"obtainAllPrivilege": false,
"obtainUserPrivilege": false,
"obtainOtherPrivilege": false,
"userInteractionRequired": false
}
]
},
"weaknesses": [
{
"source": "nvd@nist.gov",
"type": "Primary",
"description": [
{
"lang": "en",
"value": "NVD-CWE-Other"
}
]
}
],
"configurations": [
{
"nodes": [
{
"operator": "OR",
"negate": false,
"cpeMatch": [
{
"vulnerable": true,
"criteria": "cpe:2.3:a:schneider-electric:quantum_ethernet_module_140cpu65150:*:*:*:*:*:*:*:*",
"versionEndIncluding": "3.5",
"matchCriteriaId": "F46FD25F-6A66-4A01-94B6-B2C7B4A1161F"
},
{
"vulnerable": true,
"criteria": "cpe:2.3:a:schneider-electric:quantum_ethernet_module_140cpu65160:*:*:*:*:*:*:*:*",
"versionEndIncluding": "3.5",
"matchCriteriaId": "E4B260E8-8CAB-43D6-B7EB-1A47085B3301"
},
{
"vulnerable": true,
"criteria": "cpe:2.3:a:schneider-electric:quantum_ethernet_module_140cpu65260:*:*:*:*:*:*:*:*",
"versionEndIncluding": "3.5",
"matchCriteriaId": "E7407DDC-F4BC-48FB-9B0B-4BED21B82FAE"
},
{
"vulnerable": true,
"criteria": "cpe:2.3:a:schneider-electric:quantum_ethernet_module_140noe77100:*:*:*:*:*:*:*:*",
"versionEndIncluding": "3.3",
"matchCriteriaId": "3E2B9B12-772E-45B0-B696-9487C5EC9669"
},
{
"vulnerable": true,
"criteria": "cpe:2.3:a:schneider-electric:quantum_ethernet_module_140noe77100:*:*:*:*:*:*:*:*",
"versionEndIncluding": "3.4",
"matchCriteriaId": "84E9206F-0AED-4C42-849E-F8741C070234"
},
{
"vulnerable": true,
"criteria": "cpe:2.3:a:schneider-electric:quantum_ethernet_module_140noe77101:*:*:*:*:*:*:*:*",
"versionEndIncluding": "4.9",
"matchCriteriaId": "C6272D36-A9E3-4210-8998-19D65323E085"
},
{
"vulnerable": true,
"criteria": "cpe:2.3:a:schneider-electric:quantum_ethernet_module_140noe77111:*:*:*:*:*:*:*:*",
"versionEndIncluding": "5.0",
"matchCriteriaId": "0780C449-C9A7-4D83-9090-C48EB308F69F"
}
]
}
]
},
{
"nodes": [
{
"operator": "OR",
"negate": false,
"cpeMatch": [
{
"vulnerable": true,
"criteria": "cpe:2.3:a:schneider-electric:premium_ethernet_module_tsxety4103:*:*:*:*:*:*:*:*",
"versionEndIncluding": "5.0",
"matchCriteriaId": "8D5CFADB-BD77-45B2-83F6-791ECB6DCEC1"
},
{
"vulnerable": true,
"criteria": "cpe:2.3:a:schneider-electric:premium_ethernet_module_tsxety5103:*:*:*:*:*:*:*:*",
"versionEndIncluding": "5.0",
"matchCriteriaId": "BD0DA2C8-81BE-4006-B6A2-DE2B20F85771"
},
{
"vulnerable": true,
"criteria": "cpe:2.3:a:schneider-electric:premium_ethernet_module_tsxp57163m:*:*:*:*:*:*:*:*",
"versionEndIncluding": "4.9",
"matchCriteriaId": "D1F32575-37AC-4F55-904F-68AED57F8B63"
},
{
"vulnerable": true,
"criteria": "cpe:2.3:a:schneider-electric:premium_ethernet_module_tsxp572634m:*:*:*:*:*:*:*:*",
"versionEndIncluding": "4.9",
"matchCriteriaId": "7B88C30B-8748-42AA-8765-2EC8ADAD4B54"
},
{
"vulnerable": true,
"criteria": "cpe:2.3:a:schneider-electric:premium_ethernet_module_tsxp573634m:*:*:*:*:*:*:*:*",
"versionEndIncluding": "4.9",
"matchCriteriaId": "985B9868-9D59-4902-B825-387BF1F8A8A6"
},
{
"vulnerable": true,
"criteria": "cpe:2.3:a:schneider-electric:premium_ethernet_module_tsxp574634m:*:*:*:*:*:*:*:*",
"versionEndIncluding": "3.5",
"matchCriteriaId": "6DD89F76-4EB6-41D2-8646-602C13166C35"
},
{
"vulnerable": true,
"criteria": "cpe:2.3:a:schneider-electric:premium_ethernet_module_tsxp575634m:*:*:*:*:*:*:*:*",
"versionEndIncluding": "3.5",
"matchCriteriaId": "D9CCBD5A-7E9F-4204-95CB-C1C00B3B4BFF"
},
{
"vulnerable": true,
"criteria": "cpe:2.3:a:schneider-electric:premium_ethernet_module_tsxp576634m:*:*:*:*:*:*:*:*",
"versionEndIncluding": "3.5",
"matchCriteriaId": "9EDB245F-2BAF-4EA1-B6EC-E9F54C8AB4AD"
}
]
}
]
},
{
"nodes": [
{
"operator": "OR",
"negate": false,
"cpeMatch": [
{
"vulnerable": true,
"criteria": "cpe:2.3:a:schneider-electric:m340_ethernet_module_bmxnoe0100:*:*:*:*:*:*:*:*",
"versionEndIncluding": "2.3",
"matchCriteriaId": "4C1A71AC-5951-40E0-900F-E3E29AD0C791"
},
{
"vulnerable": true,
"criteria": "cpe:2.3:a:schneider-electric:m340_ethernet_module_bmxnoe0110:*:*:*:*:*:*:*:*",
"versionEndIncluding": "4.65",
"matchCriteriaId": "A7D8CC15-CFC3-4BFF-9BC0-4059FD7DCDE6"
},
{
"vulnerable": true,
"criteria": "cpe:2.3:a:schneider-electric:m340_ethernet_module_bmxp342020:*:*:*:*:*:*:*:*",
"versionEndIncluding": "2.2",
"matchCriteriaId": "76A49B2B-1353-46BF-8A03-2CD5701A1465"
},
{
"vulnerable": true,
"criteria": "cpe:2.3:a:schneider-electric:m340_ethernet_module_bmxp342030:*:*:*:*:*:*:*:*",
"versionEndIncluding": "2.2",
"matchCriteriaId": "130C136E-5762-4C25-8F66-85CC323FB04F"
}
]
}
]
},
{
"nodes": [
{
"operator": "OR",
"negate": false,
"cpeMatch": [
{
"vulnerable": true,
"criteria": "cpe:2.3:a:schneider-electric:stb_dio_ethernet_module_stbnic2212:*:*:*:*:*:*:*:*",
"versionEndIncluding": "2.10",
"matchCriteriaId": "A4EC1C87-FF50-4442-B096-6EBB70A679A9"
},
{
"vulnerable": true,
"criteria": "cpe:2.3:a:schneider-electric:stb_dio_ethernet_module_stbnip2212:*:*:*:*:*:*:*:*",
"versionEndIncluding": "2.73",
"matchCriteriaId": "76A596AB-117A-471A-8DE2-F0271370EAE5"
},
{
"vulnerable": true,
"criteria": "cpe:2.3:a:schneider-electric:stb_dio_ethernet_module_stbnip2311:*:*:*:*:*:*:*:*",
"versionEndIncluding": "3.01",
"matchCriteriaId": "1FDE9605-55A2-4B8C-B1F3-880E98328C55"
}
]
}
]
}
],
"references": [
{
"url": "http://reversemode.com/index.php?option=com_content&task=view&id=80&Itemid=1",
"source": "cve@mitre.org"
},
{
"url": "http://www.securityfocus.com/bid/51605",
"source": "cve@mitre.org"
},
{
"url": "http://www.us-cert.gov/control_systems/pdf/ICS-ALERT-11-346-01.pdf",
"source": "cve@mitre.org"
},
{
"url": "http://www.us-cert.gov/control_systems/pdf/ICS-ALERT-12-020-03.pdf",
"source": "cve@mitre.org"
},
{
"url": "http://www.us-cert.gov/control_systems/pdf/ICSA-12-018-01.pdf",
"source": "cve@mitre.org"
},
{
"url": "https://exchange.xforce.ibmcloud.com/vulnerabilities/72587",
"source": "cve@mitre.org"
}
]
}