mirror of
https://github.com/fkie-cad/nvd-json-data-feeds.git
synced 2025-05-28 17:21:36 +00:00
166 lines
7.5 KiB
JSON
166 lines
7.5 KiB
JSON
{
|
|
"id": "CVE-2024-22039",
|
|
"sourceIdentifier": "productcert@siemens.com",
|
|
"published": "2024-03-12T11:15:48.420",
|
|
"lastModified": "2024-11-21T08:55:26.327",
|
|
"vulnStatus": "Modified",
|
|
"cveTags": [],
|
|
"descriptions": [
|
|
{
|
|
"lang": "en",
|
|
"value": "A vulnerability has been identified in Cerberus PRO EN Engineering Tool (All versions < IP8), Cerberus PRO EN Fire Panel FC72x IP6 (All versions < IP6 SR3), Cerberus PRO EN Fire Panel FC72x IP7 (All versions < IP7 SR5), Cerberus PRO EN X200 Cloud Distribution IP7 (All versions < V3.0.6602), Cerberus PRO EN X200 Cloud Distribution IP8 (All versions < V4.0.5016), Cerberus PRO EN X300 Cloud Distribution IP7 (All versions < V3.2.6601), Cerberus PRO EN X300 Cloud Distribution IP8 (All versions < V4.2.5015), Cerberus PRO UL Compact Panel FC922/924 (All versions < MP4), Cerberus PRO UL Engineering Tool (All versions < MP4), Cerberus PRO UL X300 Cloud Distribution (All versions < V4.3.0001), Desigo Fire Safety UL Compact Panel FC2025/2050 (All versions < MP4), Desigo Fire Safety UL Engineering Tool (All versions < MP4), Desigo Fire Safety UL X300 Cloud Distribution (All versions < V4.3.0001), Sinteso FS20 EN Engineering Tool (All versions < MP8), Sinteso FS20 EN Fire Panel FC20 MP6 (All versions < MP6 SR3), Sinteso FS20 EN Fire Panel FC20 MP7 (All versions < MP7 SR5), Sinteso FS20 EN X200 Cloud Distribution MP7 (All versions < V3.0.6602), Sinteso FS20 EN X200 Cloud Distribution MP8 (All versions < V4.0.5016), Sinteso FS20 EN X300 Cloud Distribution MP7 (All versions < V3.2.6601), Sinteso FS20 EN X300 Cloud Distribution MP8 (All versions < V4.2.5015), Sinteso Mobile (All versions < V3.0.0). The network communication library in affected systems does not validate the length of certain X.509 certificate attributes which might result in a stack-based buffer overflow.\r\nThis could allow an unauthenticated remote attacker to execute code on the underlying operating system with root privileges."
|
|
},
|
|
{
|
|
"lang": "es",
|
|
"value": "Se ha identificado una vulnerabilidad en Cerberus PRO EN Engineering Tool (todas las versiones < IP8), Cerberus PRO EN Fire Panel FC72x (todas las versiones < IP8), Cerberus PRO EN X200 Cloud Distribution (todas las versiones < V4.0.5016), Cerberus PRO EN X300 Distribuci\u00f3n en la nube (todas las versiones < V4.2.5015), herramienta de ingenier\u00eda Sinteso FS20 EN (todas las versiones < MP8), central de incendios Sinteso FS20 EN FC20 (todas las versiones < MP8), distribuci\u00f3n en la nube Sinteso FS20 EN X200 (todas las versiones < V4.0.5016) , Sinteso FS20 EN X300 Cloud Distribution (todas las versiones "
|
|
}
|
|
],
|
|
"metrics": {
|
|
"cvssMetricV31": [
|
|
{
|
|
"source": "productcert@siemens.com",
|
|
"type": "Secondary",
|
|
"cvssData": {
|
|
"version": "3.1",
|
|
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H",
|
|
"baseScore": 10.0,
|
|
"baseSeverity": "CRITICAL",
|
|
"attackVector": "NETWORK",
|
|
"attackComplexity": "LOW",
|
|
"privilegesRequired": "NONE",
|
|
"userInteraction": "NONE",
|
|
"scope": "CHANGED",
|
|
"confidentialityImpact": "HIGH",
|
|
"integrityImpact": "HIGH",
|
|
"availabilityImpact": "HIGH"
|
|
},
|
|
"exploitabilityScore": 3.9,
|
|
"impactScore": 6.0
|
|
},
|
|
{
|
|
"source": "nvd@nist.gov",
|
|
"type": "Primary",
|
|
"cvssData": {
|
|
"version": "3.1",
|
|
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H",
|
|
"baseScore": 9.8,
|
|
"baseSeverity": "CRITICAL",
|
|
"attackVector": "NETWORK",
|
|
"attackComplexity": "LOW",
|
|
"privilegesRequired": "NONE",
|
|
"userInteraction": "NONE",
|
|
"scope": "UNCHANGED",
|
|
"confidentialityImpact": "HIGH",
|
|
"integrityImpact": "HIGH",
|
|
"availabilityImpact": "HIGH"
|
|
},
|
|
"exploitabilityScore": 3.9,
|
|
"impactScore": 5.9
|
|
}
|
|
]
|
|
},
|
|
"weaknesses": [
|
|
{
|
|
"source": "productcert@siemens.com",
|
|
"type": "Primary",
|
|
"description": [
|
|
{
|
|
"lang": "en",
|
|
"value": "CWE-120"
|
|
}
|
|
]
|
|
}
|
|
],
|
|
"configurations": [
|
|
{
|
|
"nodes": [
|
|
{
|
|
"operator": "OR",
|
|
"negate": false,
|
|
"cpeMatch": [
|
|
{
|
|
"vulnerable": true,
|
|
"criteria": "cpe:2.3:a:siemens:cerberus_pro_en_engineering_tool:*:*:*:*:*:*:*:*",
|
|
"versionEndExcluding": "ip8",
|
|
"matchCriteriaId": "51481F41-444E-4B78-A15F-516C7EC2F50D"
|
|
},
|
|
{
|
|
"vulnerable": true,
|
|
"criteria": "cpe:2.3:a:siemens:cerberus_pro_en_fire_panel_fc72x:*:*:*:*:*:*:*:*",
|
|
"versionEndExcluding": "ip8",
|
|
"matchCriteriaId": "7E15F412-20D3-417B-9DD7-F9861D44644B"
|
|
},
|
|
{
|
|
"vulnerable": true,
|
|
"criteria": "cpe:2.3:a:siemens:cerberus_pro_en_x200_cloud_distribution:*:*:*:*:*:*:*:*",
|
|
"versionEndExcluding": "4.0.5016",
|
|
"matchCriteriaId": "F4595AA9-ADC3-49EE-9767-2043DBB7FEE4"
|
|
},
|
|
{
|
|
"vulnerable": true,
|
|
"criteria": "cpe:2.3:a:siemens:cerberus_pro_en_x300_cloud_distribution:*:*:*:*:*:*:*:*",
|
|
"versionEndExcluding": "4.2.5015",
|
|
"matchCriteriaId": "C2EC2222-3208-4677-9DC0-84EF66D3C44B"
|
|
},
|
|
{
|
|
"vulnerable": true,
|
|
"criteria": "cpe:2.3:a:siemens:sinteso_fs20_en_engineering_tool:*:*:*:*:*:*:*:*",
|
|
"versionEndExcluding": "mp8",
|
|
"matchCriteriaId": "AD41968F-E374-41DB-9B43-551693339918"
|
|
},
|
|
{
|
|
"vulnerable": true,
|
|
"criteria": "cpe:2.3:a:siemens:sinteso_fs20_en_fire_panel_fc20:*:*:*:*:*:*:*:*",
|
|
"versionEndExcluding": "mp8",
|
|
"matchCriteriaId": "82F92204-A977-48F7-9247-B283D9371CCA"
|
|
},
|
|
{
|
|
"vulnerable": true,
|
|
"criteria": "cpe:2.3:a:siemens:sinteso_fs20_en_x200_cloud_distribution:*:*:*:*:*:*:*:*",
|
|
"versionEndExcluding": "4.0.5016",
|
|
"matchCriteriaId": "40675EA2-2B5A-490D-989A-2726941BDA6B"
|
|
},
|
|
{
|
|
"vulnerable": true,
|
|
"criteria": "cpe:2.3:a:siemens:sinteso_fs20_en_x300_cloud_distribution:*:*:*:*:*:*:*:*",
|
|
"versionEndExcluding": "4.2.5015",
|
|
"matchCriteriaId": "BE335B38-42D4-4BB4-A549-FDEB897A56AD"
|
|
},
|
|
{
|
|
"vulnerable": true,
|
|
"criteria": "cpe:2.3:a:siemens:sinteso_mobile:*:*:*:*:*:*:*:*",
|
|
"versionEndExcluding": "3.0.0",
|
|
"matchCriteriaId": "AC5EDF20-9665-4487-AF9E-2E4FF12E7BBD"
|
|
}
|
|
]
|
|
}
|
|
]
|
|
}
|
|
],
|
|
"references": [
|
|
{
|
|
"url": "https://cert-portal.siemens.com/productcert/html/ssa-225840.html",
|
|
"source": "productcert@siemens.com",
|
|
"tags": [
|
|
"Patch",
|
|
"Vendor Advisory"
|
|
]
|
|
},
|
|
{
|
|
"url": "https://cert-portal.siemens.com/productcert/html/ssa-953710.html",
|
|
"source": "productcert@siemens.com"
|
|
},
|
|
{
|
|
"url": "https://cert-portal.siemens.com/productcert/html/ssa-225840.html",
|
|
"source": "af854a3a-2127-422b-91ae-364da2661108",
|
|
"tags": [
|
|
"Patch",
|
|
"Vendor Advisory"
|
|
]
|
|
},
|
|
{
|
|
"url": "https://cert-portal.siemens.com/productcert/html/ssa-953710.html",
|
|
"source": "af854a3a-2127-422b-91ae-364da2661108"
|
|
}
|
|
]
|
|
} |