2022-12-19 10:00:39 +00:00
{
2023-07-26 06:00:36 +00:00
"data_version" : "4.0" ,
2022-12-19 10:00:39 +00:00
"data_type" : "CVE" ,
"data_format" : "MITRE" ,
"CVE_data_meta" : {
"ID" : "CVE-2022-4608" ,
2023-07-26 06:00:36 +00:00
"ASSIGNER" : "cybersecurity@hitachienergy.com" ,
"STATE" : "PUBLIC"
2022-12-19 10:00:39 +00:00
} ,
"description" : {
"description_data" : [
{
"lang" : "eng" ,
2023-07-26 06:00:36 +00:00
"value" : "A vulnerability exists in HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-3. After session resumption interval is expired an RTU500 initiated update of session parameters causes an unexpected restart due to a stack overflow."
}
]
} ,
"problemtype" : {
"problemtype_data" : [
{
"description" : [
{
"lang" : "eng" ,
2024-09-24 16:00:34 +00:00
"value" : "CWE-787 Out-of-bounds Write" ,
"cweId" : "CWE-787"
2023-07-26 06:00:36 +00:00
}
]
}
]
} ,
"affects" : {
"vendor" : {
"vendor_data" : [
{
"vendor_name" : "Hitachi Energy" ,
"product" : {
"product_data" : [
{
"product_name" : "RTU500 series" ,
"version" : {
"version_data" : [
{
"version_value" : "not down converted" ,
"x_cve_json_5_version_data" : {
"versions" : [
{
"status" : "affected" ,
"version" : "RTU500 series CMU Firmware version 13.3.1"
} ,
{
"status" : "affected" ,
"version" : "RTU500 series CMU Firmware version 13.3.2"
} ,
{
"status" : "unaffected" ,
"version" : "RTU500 series CMU Firmware version 13.3.3"
} ,
{
"status" : "unaffected" ,
"version" : "RTU500 series CMU Firmware version 13.4.1"
}
] ,
"defaultStatus" : "unaffected"
}
}
]
}
}
]
}
}
]
}
} ,
"references" : {
"reference_data" : [
{
2024-09-24 16:00:34 +00:00
"url" : "https://publisher.hitachienergy.com/preview?DocumentID=8DBD000121&LanguageCode=en&DocumentPartId=&Action=Launch" ,
2023-07-26 06:00:36 +00:00
"refsource" : "MISC" ,
2024-09-24 16:00:34 +00:00
"name" : "https://publisher.hitachienergy.com/preview?DocumentID=8DBD000121&LanguageCode=en&DocumentPartId=&Action=Launch"
2023-07-26 06:00:36 +00:00
}
]
} ,
"generator" : {
"engine" : "Vulnogram 0.1.0-dev"
} ,
"source" : {
"discovery" : "UNKNOWN"
} ,
"configuration" : [
{
"lang" : "en" ,
"supportingMedia" : [
{
"base64" : false ,
"type" : "text/html" ,
2024-09-24 16:00:34 +00:00
"value" : "RTU500 series with HCI IEC 60870-5-104 and IEC 62351-3 configured and enabled.\n\n<br>"
2023-07-26 06:00:36 +00:00
}
] ,
2024-09-24 16:00:34 +00:00
"value" : "RTU500 series with HCI IEC 60870-5-104 and IEC 62351-3 configured and enabled."
2023-07-26 06:00:36 +00:00
}
] ,
"work_around" : [
{
"lang" : "en" ,
"supportingMedia" : [
{
"base64" : false ,
"type" : "text/html" ,
2024-09-24 16:00:34 +00:00
"value" : "Disable the HCI IEC 60870-5-104 function or its IEC 62351-3 feature if it is not used.\n\n<br>"
2023-07-26 06:00:36 +00:00
}
] ,
2024-09-24 16:00:34 +00:00
"value" : "Disable the HCI IEC 60870-5-104 function or its IEC 62351-3 feature if it is not used."
2023-07-26 06:00:36 +00:00
}
] ,
"solution" : [
{
"lang" : "en" ,
"supportingMedia" : [
{
"base64" : false ,
"type" : "text/html" ,
2024-09-24 16:00:34 +00:00
"value" : "Update to CMU Firmware versions 13.3.3 or 13.4.1.\n\n<br>"
2023-07-26 06:00:36 +00:00
}
] ,
2024-09-24 16:00:34 +00:00
"value" : "Update to CMU Firmware versions 13.3.3 or 13.4.1."
2023-07-26 06:00:36 +00:00
}
] ,
"impact" : {
"cvss" : [
{
"attackComplexity" : "LOW" ,
"attackVector" : "NETWORK" ,
"availabilityImpact" : "HIGH" ,
"baseScore" : 7.5 ,
"baseSeverity" : "HIGH" ,
"confidentialityImpact" : "NONE" ,
"integrityImpact" : "NONE" ,
"privilegesRequired" : "NONE" ,
"scope" : "UNCHANGED" ,
"userInteraction" : "NONE" ,
"vectorString" : "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H" ,
"version" : "3.1"
2022-12-19 10:00:39 +00:00
}
]
}
}