mirror of
https://github.com/CVEProject/cvelist.git
synced 2025-07-29 05:56:59 +00:00
147 lines
5.7 KiB
JSON
147 lines
5.7 KiB
JSON
{
|
|
"data_version": "4.0",
|
|
"data_type": "CVE",
|
|
"data_format": "MITRE",
|
|
"CVE_data_meta": {
|
|
"ID": "CVE-2022-4608",
|
|
"ASSIGNER": "cybersecurity@hitachienergy.com",
|
|
"STATE": "PUBLIC"
|
|
},
|
|
"description": {
|
|
"description_data": [
|
|
{
|
|
"lang": "eng",
|
|
"value": "A vulnerability exists in HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-3. After session resumption interval is expired an RTU500 initiated update of session parameters causes an unexpected restart due to a stack overflow."
|
|
}
|
|
]
|
|
},
|
|
"problemtype": {
|
|
"problemtype_data": [
|
|
{
|
|
"description": [
|
|
{
|
|
"lang": "eng",
|
|
"value": "CWE-787 Out-of-bounds Write",
|
|
"cweId": "CWE-787"
|
|
}
|
|
]
|
|
}
|
|
]
|
|
},
|
|
"affects": {
|
|
"vendor": {
|
|
"vendor_data": [
|
|
{
|
|
"vendor_name": "Hitachi Energy",
|
|
"product": {
|
|
"product_data": [
|
|
{
|
|
"product_name": "RTU500 series",
|
|
"version": {
|
|
"version_data": [
|
|
{
|
|
"version_value": "not down converted",
|
|
"x_cve_json_5_version_data": {
|
|
"versions": [
|
|
{
|
|
"status": "affected",
|
|
"version": "RTU500 series CMU Firmware version 13.3.1"
|
|
},
|
|
{
|
|
"status": "affected",
|
|
"version": "RTU500 series CMU Firmware version 13.3.2"
|
|
},
|
|
{
|
|
"status": "unaffected",
|
|
"version": "RTU500 series CMU Firmware version 13.3.3"
|
|
},
|
|
{
|
|
"status": "unaffected",
|
|
"version": "RTU500 series CMU Firmware version 13.4.1"
|
|
}
|
|
],
|
|
"defaultStatus": "unaffected"
|
|
}
|
|
}
|
|
]
|
|
}
|
|
}
|
|
]
|
|
}
|
|
}
|
|
]
|
|
}
|
|
},
|
|
"references": {
|
|
"reference_data": [
|
|
{
|
|
"url": "https://publisher.hitachienergy.com/preview?DocumentID=8DBD000121&LanguageCode=en&DocumentPartId=&Action=Launch",
|
|
"refsource": "MISC",
|
|
"name": "https://publisher.hitachienergy.com/preview?DocumentID=8DBD000121&LanguageCode=en&DocumentPartId=&Action=Launch"
|
|
}
|
|
]
|
|
},
|
|
"generator": {
|
|
"engine": "Vulnogram 0.1.0-dev"
|
|
},
|
|
"source": {
|
|
"discovery": "UNKNOWN"
|
|
},
|
|
"configuration": [
|
|
{
|
|
"lang": "en",
|
|
"supportingMedia": [
|
|
{
|
|
"base64": false,
|
|
"type": "text/html",
|
|
"value": "RTU500 series with HCI IEC 60870-5-104 and IEC 62351-3 configured and enabled.\n\n<br>"
|
|
}
|
|
],
|
|
"value": "RTU500 series with HCI IEC 60870-5-104 and IEC 62351-3 configured and enabled."
|
|
}
|
|
],
|
|
"work_around": [
|
|
{
|
|
"lang": "en",
|
|
"supportingMedia": [
|
|
{
|
|
"base64": false,
|
|
"type": "text/html",
|
|
"value": "Disable the HCI IEC 60870-5-104 function or its IEC 62351-3 feature if it is not used.\n\n<br>"
|
|
}
|
|
],
|
|
"value": "Disable the HCI IEC 60870-5-104 function or its IEC 62351-3 feature if it is not used."
|
|
}
|
|
],
|
|
"solution": [
|
|
{
|
|
"lang": "en",
|
|
"supportingMedia": [
|
|
{
|
|
"base64": false,
|
|
"type": "text/html",
|
|
"value": "Update to CMU Firmware versions 13.3.3 or 13.4.1.\n\n<br>"
|
|
}
|
|
],
|
|
"value": "Update to CMU Firmware versions 13.3.3 or 13.4.1."
|
|
}
|
|
],
|
|
"impact": {
|
|
"cvss": [
|
|
{
|
|
"attackComplexity": "LOW",
|
|
"attackVector": "NETWORK",
|
|
"availabilityImpact": "HIGH",
|
|
"baseScore": 7.5,
|
|
"baseSeverity": "HIGH",
|
|
"confidentialityImpact": "NONE",
|
|
"integrityImpact": "NONE",
|
|
"privilegesRequired": "NONE",
|
|
"scope": "UNCHANGED",
|
|
"userInteraction": "NONE",
|
|
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
|
|
"version": "3.1"
|
|
}
|
|
]
|
|
}
|
|
} |