cvelist/2022/4xxx/CVE-2022-4608.json
2024-09-24 16:00:34 +00:00

147 lines
5.7 KiB
JSON

{
"data_version": "4.0",
"data_type": "CVE",
"data_format": "MITRE",
"CVE_data_meta": {
"ID": "CVE-2022-4608",
"ASSIGNER": "cybersecurity@hitachienergy.com",
"STATE": "PUBLIC"
},
"description": {
"description_data": [
{
"lang": "eng",
"value": "A vulnerability exists in HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-3. After session resumption interval is expired an RTU500 initiated update of session parameters causes an unexpected restart due to a stack overflow."
}
]
},
"problemtype": {
"problemtype_data": [
{
"description": [
{
"lang": "eng",
"value": "CWE-787 Out-of-bounds Write",
"cweId": "CWE-787"
}
]
}
]
},
"affects": {
"vendor": {
"vendor_data": [
{
"vendor_name": "Hitachi Energy",
"product": {
"product_data": [
{
"product_name": "RTU500 series",
"version": {
"version_data": [
{
"version_value": "not down converted",
"x_cve_json_5_version_data": {
"versions": [
{
"status": "affected",
"version": "RTU500 series CMU Firmware version 13.3.1"
},
{
"status": "affected",
"version": "RTU500 series CMU Firmware version 13.3.2"
},
{
"status": "unaffected",
"version": "RTU500 series CMU Firmware version 13.3.3"
},
{
"status": "unaffected",
"version": "RTU500 series CMU Firmware version 13.4.1"
}
],
"defaultStatus": "unaffected"
}
}
]
}
}
]
}
}
]
}
},
"references": {
"reference_data": [
{
"url": "https://publisher.hitachienergy.com/preview?DocumentID=8DBD000121&LanguageCode=en&DocumentPartId=&Action=Launch",
"refsource": "MISC",
"name": "https://publisher.hitachienergy.com/preview?DocumentID=8DBD000121&LanguageCode=en&DocumentPartId=&Action=Launch"
}
]
},
"generator": {
"engine": "Vulnogram 0.1.0-dev"
},
"source": {
"discovery": "UNKNOWN"
},
"configuration": [
{
"lang": "en",
"supportingMedia": [
{
"base64": false,
"type": "text/html",
"value": "RTU500 series with HCI IEC 60870-5-104 and IEC 62351-3 configured and enabled.\n\n<br>"
}
],
"value": "RTU500 series with HCI IEC 60870-5-104 and IEC 62351-3 configured and enabled."
}
],
"work_around": [
{
"lang": "en",
"supportingMedia": [
{
"base64": false,
"type": "text/html",
"value": "Disable the HCI IEC 60870-5-104 function or its IEC 62351-3 feature if it is not used.\n\n<br>"
}
],
"value": "Disable the HCI IEC 60870-5-104 function or its IEC 62351-3 feature if it is not used."
}
],
"solution": [
{
"lang": "en",
"supportingMedia": [
{
"base64": false,
"type": "text/html",
"value": "Update to CMU Firmware versions 13.3.3 or 13.4.1.\n\n<br>"
}
],
"value": "Update to CMU Firmware versions 13.3.3 or 13.4.1."
}
],
"impact": {
"cvss": [
{
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 7.5,
"baseSeverity": "HIGH",
"confidentialityImpact": "NONE",
"integrityImpact": "NONE",
"privilegesRequired": "NONE",
"scope": "UNCHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
"version": "3.1"
}
]
}
}