"CVE_data_meta": {
"ASSIGNER": "ics-cert@hq.dhs.gov",
"DATE_PUBLIC": "2021-09-27T15:34:00.000Z",
"ID": "CVE-2021-38450",
"STATE": "PUBLIC",
"TITLE": "Trane Tracer Code Injection"
},
"affects": {
"vendor": {
"vendor_data": [
{
"product": {
"product_data": [
{
"product_name": "Tracer SC",
"version": {
"version_data": [
{
"version_affected": "<",
"version_name": "All",
"version_value": "4.4 SP7"
}
]
}
},
{
"product_name": "Tracer SC+",
"version": {
"version_data": [
{
"version_affected": "<",
"version_name": "All",
"version_value": "5.5 SP3"
}
]
}
},
{
"product_name": "Tracer Concierge",
"version": {
"version_data": [
{
"version_affected": "<",
"version_name": "All",
"version_value": "5.5 SP3"
}
]
}
}
]
},
"vendor_name": "Trane"
}
]
}
},
"credit": [
{
"lang": "eng",
"value": "Trane reported this vulnerability to CISA."
}
],
"data_format": "MITRE",
"data_type": "CVE",
"data_version": "4.0",
"description": {
"description_data": [
{
"lang": "eng",
"value": "The affected controllers do not properly sanitize the input containing code syntax. As a result, an attacker could craft code to alter the intended controller flow of the software."
}
]
},
"generator": {
"engine": "Vulnogram 0.0.9"
},
"impact": {
"cvss": {
"attackComplexity": "LOW",
"attackVector": "NETWORK",
"availabilityImpact": "HIGH",
"baseScore": 9.9,
"baseSeverity": "CRITICAL",
"confidentialityImpact": "LOW",
"integrityImpact": "HIGH",
"privilegesRequired": "LOW",
"scope": "CHANGED",
"userInteraction": "NONE",
"vectorString": "CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:C/C:L/I:H/A:H",
"version": "3.1"
}
},
"problemtype": {
"problemtype_data": [
{
"description": [
{
"lang": "eng",
"value": "CWE-94 Improper Control of Generation of Code ('Code Injection')"
}
]
}
]
},
"references": {
"reference_data": [
{
"name": "https://us-cert.cisa.gov/ics/advisories/icsa-21-266-02",
"refsource": "CONFIRM",
"url": "https://us-cert.cisa.gov/ics/advisories/icsa-21-266-02"
}
]
},
"solution": [
{
"lang": "eng",
"value": "Affected users should contact a Trane representative to install updated firmware or request additional information. Please reference Trane service database number HUB-205962 when contacting the Trane office.\n\nTracer SC is no longer actively developed, tested, or sold. Tracer SC will be considered end-of-life on December 31, 2022. Trane recommends identifying a migration plan for replacing the Tracer SC controller with the next-generation Tracer SC+ controller. Tracer SC+ can function as a drop-in replacement for Tracer SC, providing significant updates to security capabilities.\n\nTrane has identified the following specific mitigations:\n\nTracer SC: Upgrade to v4.4 SP7 or later\nTracer SC+: Upgrade to v5.5 SP3 or later\nTracer Concierge: Upgrade to v5.5 SP3 or later"
}
],
"source": {
"advisory": "https://us-cert.cisa.gov/ics/advisories/icsa-21-266-02",
"discovery": "UNKNOWN"
}
}